CARE AND HANDLING 

OF SPRINKLERS

Page 1 of 4

Form No. F_091699     18.10.11    Rev 16.1.P65

SPRINKLERS ARE FRAGILE - HANDLE WITH CARE!

General Handling and Storage:

• 

Store sprinklers in a cool, dry place.

• 

Protect sprinklers during storage, transport, handling, and after installation.

• 

Use the original shipping containers. DO NOT place sprinklers loose in boxes, bins, 

or buckets.

• 

Keep sprinklers separated at all times. DO NOT allow metal parts to contact sprinkler 

operating elements.

For Pre-Assembled Drops:

• 

Protect sprinklers during handling and after installation.

• 

For recessed assemblies, use the protective sprinkler cap (Viking Part Number 10364).

Sprinklers with Protective Shields or Caps:

• 

DO NOT remove shields or caps until after sprinkler installation and there no longer is 

potential for mechanical damage to the sprinkler operating elements.

• 

Sprinkler shields or caps MUST be removed BEFORE placing the system in 

service!

• 

Remove the sprinkler shield by carefully pulling it apart where it is snapped together.

• 

Remove the cap by turning it slightly and pulling it off the sprinkler.

Sprinkler Installation:

• 

DO NOT use the sprinkler deflector or operating element to start or thread the sprinkler 

into a fitting.

• 

Use only the designated sprinkler head wrench!

 Refer to the current sprinkler tech-

nical data page to determine the correct wrench for the model of sprinkler used.

• 

DO NOT install sprinklers onto piping at the floor level.

• 

Install sprinklers after the piping is in place to prevent mechanical damage.

• 

DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings, pipe, 

or couplings in close proximity to sprinklers. Sprinklers can be damaged from direct or 

indirect impacts.

• 

DO NOT attempt to remove drywall, paint, etc., from sprinklers.

• 

Take care not to over-tighten the sprinkler and/or damage its operating parts! 

Maximum Torque:  

1/2” NPT:   14 ft-lbs. (19.0 N-m)        
3/4” NPT:   20 ft-lbs. (27.1 N-m)         
1” NPT:   30 ft-lbs. (40.7 N-m)

 WARNING

Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed. Never install sprinklers 

that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature allowed. Sprinklers that 

have been painted in the field must be replaced per NFPA 13. Protect sprinklers from paint and paint overspray in accordance with 

the installation standards. Do not clean sprinklers with soap and water, ammonia, or any other cleaning fluid. Do not use adhesives 

or solvents on sprinklers or their operating elements.

Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance 

instructions. For additional product and system information Viking data pages and installation instructions are available on 

the Viking Web site at www.vikinggroupinc.com.

CORRECT

(Original container used)

INCORRECT

(Placed loose in box)

CORRECT

(Protected with caps)

INCORRECT

(Protective caps not used)

CORRECT

(Piping is in place at the 

ceiling)

INCORRECT

(Sprinkler at floor level)

CORRECT

(Special installation 

wrenches)

INCORRECT

(Designated wrench not 

used)

Replaces Form No. F_091699 Rev 16.1

(Added P65 Warning)

Summary of Contents for M

Page 1: ...ULus listed as corrosion resistant as indicated in the Approval Chart 2 LISTINGS AND APPROVALS cULus Listed Category VGYZ NYC Approved MEA 89 92 E Volume 29 NOTE International approval certificates are available upon request Refer to the Approval Chart and Design Criteria for cULus listing requirements that must be followed 3 TECHNICAL DATA Specifications Minimum Operating Pressure 7 PSI 0 5 bar R...

Page 2: ...ned to be installed in accordance with recognized installation standards Deviation from the standards or any alteration to the nozzle after it leaves the factory including but not limited to painting plating coating or modification may render the unit inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RAT...

Page 3: ...mm 2 8 40 2 17 32 64 3 A1 B1 A1 B1 21376 150 1 2 15 mm 3 8 10 mm 2 8 40 2 1 2 63 5 A1 B1 A1 B1 5 16 Orifice7 21377 60 1 2 15 mm 5 16 1 9 27 2 11 16 68 3 A1 B1 A1 B1 21378 90 1 2 15 mm 5 16 1 9 27 2 9 16 65 1 A1 B1 A1 B1 21379 120 1 2 15 mm 5 16 1 9 27 2 17 32 64 3 A1 B1 A1 B1 21380 150 1 2 15 mm 5 16 1 9 27 2 1 2 63 5 A1 B1 A1 B1 1 4 Orifice7 21381 60 1 2 15 mm 1 4 1 4 20 2 11 16 68 3 A1 B1 A1 B1 ...

Page 4: ...orrosion resistant sprinklers and spray nozzles must be installed when subject to corrosive atmospheres When installing corrosion resistant nozzles take care not to damage the corrosion resistant coating F Spray nozzles must be installed after the piping is in place to prevent mechanical damage G Sprinklers and spray nozzles must be protected from mechanical damage Where open sprinklers are used c...

Page 5: ...nstallation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to NFPA 25 and the Authority Having Jurisdiction for the specified period of time after which testing and or replacement is required Never attempt to repair or reassemble a sprinkler Sprinklers that have operated cannot be reassembled or re used but must be replaced When replacem...

Page 6: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 7: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 8: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 9: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 10: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...