TECHNICAL DATA
January 12, 2007
Deluge Devices 270g
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]
Table 2 - Dip Switch Settings for System Configuration Modes
DIP SWITCH SETTINGS
MODE DESCRIPTION
CONFIGURATION
OPERATION
1
2
3
4
5
6
1
Single Hazard -
Two Zone
One release circuit.
Two detection circuits.
Activation of EITHER detection cir-
cuit energizes the release circuit.
OFF OFF OFF OFF OFF
NOT
USED
2
Single Hazard -
Cross Zone
One release circuit.
Two detection circuits.
BOTH detection circuits must acti-
vate to energize the release circuit.
ON OFF OFF OFF OFF
3
Dual Hazard
- Combined
Release
Two release circuits.
Two detection circuits.
Activation of EITHER detection
circuit energizes BOTH release cir-
cuits.
OFF ON OFF OFF OFF
4
Dual Hazard -
Split Release
Two release circuits.
Two detection circuits.
Activation of detection circuit No.
1 energizes release circuit No. 1
Activation of detection circuit No. 2
energizes release circuit No. 2
ON ON OFF OFF OFF
Note
: Dip Switches 3, 4 and 5 MUST be OFF to disable timer capabilities of the panel. For information concerning timer capabilities,
refer to PAR-3 Owners Manual. Also, refer to installation standards, Technical Data, and all Authorities Having Jurisdiction when using
timer confi gurations.
Table 3 - Charts show Output and Relay Module Circuits Activated by Detection Circuits
OBSOLETE