The VB-4DA analog output module has four output channels.  The output channels take in a 
digital value and output an equivalent analog (voltage or current) signal.  This is called a D/A 
conversion.  The VB-4DA has maximum resolution of 8 bits.

The selection of voltage or current based output is by user wiring.  Analog ranges of 0 ~ 10 V 
DC and/or 0 ~ 20 mA  maybe selected independently for each channel.

The VB-4DA analog output module is attached as an extension to the VB series Programmable 
Logical Controller (hereinafter referred to as “PLC”), and the VB-4DA is attached as an 
extension to the VB series PLC Main Unit.  Each VB-4DA functions as a special module 
which transfers data with the PLC using the FROM / TO instructions, and would not occupy 
any input or output point.  Up to 8 special modules can be connected to single VB2 series PLC; 
a single VB0 series PLC can connect with two special modules.

2.  Specifications

<< Power Requirement >>

 

5 V DC, 30 mA (for internal control)

          Supplied from PLC Main Unit (or Expansion Unit / VB-PWR) via its extension cable.

   

○  From a Main Unit:

          [ (The amount of Expansion Modules) + (The amount of Special Modules) X 2  ] 

 4

   

○  From an Expansion Unit or VB-PWR:

          [ (The amount of Expansion Modules) + (The amount of Special Modules) X 2  ] 

 12

 

24 V DC (+20% / -15%), 120 mA Max.  (for analog signal output)

Supplied from external power supply or 24 V DC output of PLC.

<< Analog Output Performance Specifications >>

Item

Voltage Output

Current Output

Voltage or Current outputs are selected by BFM #0 & different terminals

Mode

0

1

2

4

5

Analog Output Range (DC)

0 ~ +10 V

0 ~ +5 V

+1 ~ +5 V

0 ~ +20 mA +4 ~ +20 mA

Digital Input Range

0 ~ +250

0 ~ +250

External Load Resistance

500 Ω ~ 1 MΩ

500 Ω or less

Resolution

40 mV

20 mV

16 mV

80 μA

64 μA

Overall Accuracy

± 1% (full scale)

Conversion Speed

0.8 ms / 4 points

Isolation

Photocoupler isolation between analog and digital circuits.  

DC/DC converter isolates of power from its power source.  

No isolation between analog channels.

----------------------------------------------------------------  

  2   

 ----------------------------------------------------------------

Summary of Contents for VB - 4DA

Page 1: ...ion of the VB 4DA analog output module always consult a professional electrical engineer who is qualified and trained to the local and national standards If in doubt about the operation or use of the...

Page 2: ...VB2 series PLC a single VB0 series PLC can connect with two special modules 2 Specifications Power Requirement 5 V DC 30 mA for internal control Supplied from PLC Main Unit or Expansion Unit VB PWR vi...

Page 3: ...tput 0 5 V DC voltage output 1 5 V DC voltage output 10V 5V 5V 1V 0 Digital Input 250 0 Digital Input 250 0 Digital Input 250 Mode 4 Mode 5 0 20 mA DC current output 4 20 mA DC current output 20mA 20m...

Page 4: ...unding 100 or less 2 If electrical noise or a voltage ripple exists at the output must connect a smoothing capacitor of 0 1 0 47 F 25 V 3 Connect the terminal on the VB 4DA with the terminal on the Ma...

Page 5: ...n Unit When X0 OFF the instruction will not be performed but the data which was read previously will still remain D FNC 79 TO P Special module BFM write in Device X Y M S KnX KnY KnM KnS T C D SD P V...

Page 6: ...voltage output mode 0 V 5 V O 2 Sets the channel to voltage output mode 1 V 5 V O 4 Sets the channel to current output mode 4 mA 20 mA O 5 Sets the channel to current output mode 0 mA 20 mA Switching...

Page 7: ...position In this program the BFM 0 H1245 The digit 1 5 CH1 will be a 4 mA 20 mA current output The digit 2 4 CH2 will be a 0 mA 20 mA current output The digit 3 2 CH3 will be a 1 V 5 V voltage output...

Page 8: ...connected on VB 4DA analog output module Refer to the Chapter 4 Wiring Check that the VB system configuration rules have not been broken i e the number of modules does not exceed 8 Ensure that the cor...

Reviews: