Supply voltage
Dual voltage 230/400 V~ selectable
Permissible supply voltage variations
+10% -15%
Maximum current
12 Amp AC3
Overload adjustment
1-13 Amp
Underload adjustment
<0,5 Amp
Level transducer
4-20 mA, two wires type
Transducer range
2, 3, 4, 5, 6, 7, 8, 9 y 10 m
Precision
±0,1 m (±0,01 m for 2 m transducer)
Input connection (power)
Direct to main switch
Output connection (motors)
Direct to contactor 4 mm²
Fixed
Clevis wall mounting
Weight approx.
3,7 Kg
Specifi cations
Troubleshooting
Mounted on a wall
Clevis mounting in detail
Clevis screws to box
Clevis
screws
to wall
Box
(Backside)
CLEVIS
Depth: 120 mm.
Problem
Cause
Solution
The system doesn’t work
•
and the power-on pilot light
is off while main power
supply voltage is present.
Blown control fuse.
•
Wrong input connection
•
Phase failure.
•
Supply over-voltage.
•
Replace with appropiate fuse.
•
Connect accurately.
•
Check phases.
•
Verify voltage.
•
The system is working but
•
the contactor does not
activated.
Voltage selection error.
•
Verify voltage selection.
•
Pump alarm trips.
•
Low overcurrent adjustment.
•
Input phase failure.
•
Anormal excessive motor
•
consumption.
Low current consumption <0,5 A.
•
Klixon input not use.
•
Check motor consumption and adjust
•
the current.
Check three supply phases.
•
Verify pump. The pump motor is
•
overloaded.
Check pump.
•
Short-circuit the non used Klixon
•
inputs.
Display shows “Err-SEn”
•
message.
The transducer isn’t connected
•
Transducer current is <2 mA.
•
Connect the 4-20 mA transducer.
•
Check transducer.
•