Installation Guide                                                                                                              

MX1

 Fire Alarm System (NZ) 

LT0360 ISSUE 2.43 

29 NOVEMBER 2017 

PAGE 9 

Mini-Gen 

Mini-Gen is an alternative tone generator to  
T-GEN 50, but with lower power and fewer 
facilities. 

The 

MX1

 Slimline cabinet gear plate has 

mounting footprints for two Mini-Gens, 
overlapped with the T-GEN 50 footprint.  The 
first Mini-Gen should be mounted in the lower 
position, so that it is earthed by the metal 
standoff.  The second Mini-Gen is mounted 
on plastic standoffs, and should be earthed 
to the first Mini-Gen as shown in Figure 9. 
 
On the 15U cabinet gear plate both Mini-
Gens are mounted on plastic stand-offs.  
Earth the Mini-Gens using the spare earth 
lead included in the panel. 

Mini-Gens must be connected to the ANC3 
relay output since this has sufficient current 
rating.  This relay can be configured for full 
supervision of loudspeaker wiring, using the 
27k

 EOLRs provided with the 

MX1

All Mini-Gens must have their 2W 
supervision link fitted.  If only one Mini-Gen is 
used, the unused 27k

 EOLRs must be 

connected to its DC terminals so that there 
are still three EOLRs in total. 

The 

MX1

 

must be configured to have “ANC3” 

supervision enabled for the ANC3 relay. 

 

 

Figure 9 

– Wiring Ancillary Relay to Mini-Gen(s) 

 

Multiple Branched Loads 

Ancillary relay ANC3 can supervise wiring to 
controlled loads on up to three branches.  This 
output can switch loads up to 5A resistive at 
30V.  Figure 10 shows the necessary wiring. 

The loads must all be isolated with diodes as 
shown in the figure.  A suitable diode for loads 
up to 1A each is 1N5404. 

Inductive loads such as bells must have 
suppression capacitors or diodes fitted as well. 

For a single branch, the EOLR is 9.1k

.  For 

two branches, each EOLR is 18k

.  For three 

branches, each EOLR is 27k

Suitable EOLRs are supplied with the 

MX1

The 

MX1

 

must be configured to have “ANC3” 

supervision enabled for the ANC3 relay. 

 

+

-

+

-

+

-

+

-

+

-

+

-

EOLR

EOLR

EOLR

Diode 

isolated 

loads

M

X

1

 C

O

N

T

R

O

L

L

E

R

A

N

C

 R

E

L

A

Y

 1

A

N

C

 R

E

L

A

Y

 2

A

N

C

 R

E

L

A

Y

 3

0V

SUP

NC

C

VBF+

NO

 

Figure 10 

– Wiring for multiple branched loads with supervision 

2 W link

fitted

Optional Control of Alert

2 W link

fitted

G

P

 O

u

tp

u

t

MINI GEN

MK2

MINI GEN

MK2

+

-

LINE 

OUT

+

-

LINE 

OUT

27k EOLR on 

100V line

27k EOLRs 

on 

100V line

Optionally link SYNC terminals if 

tones must be synchronised

M

X

1

 C

O

N

T

R

O

L

L

E

R

A

N

C

 R

E

L

A

Y

 1

A

N

C

 R

E

L

A

Y

 2

A

N

C

 R

E

L

A

Y

 3

0V

SUP

NC

C

VBF+

NO

DC 

IN

+

VE

- VE

SUP

+

ALERT

-

SYNC -

Earth second Mini-Gen 

to first Mini-Gen

DC 

IN

+

VE

- VE

SUP

+

ALERT

-

SYNC -

Mount PCB with M3 crosshead 

screw to metal standoff here for 

earthing to gearplate 

(all other pcb standoffs used are 

plastic)

Summary of Contents for MX1

Page 1: ... REMOVE POWER TO MX1 PANEL BEFORE PLUGGING IN OR DISCONNECTING MODULES SUCH AS THE 16 ZONE LED DISPLAY LCD KEYBOARD MX LOOP CARD ETC 2017 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice LT0360 V2 43 ...

Page 2: ... moderate ambient temperature 45 C absolute maximum Not be subject to outdoor conditions without suitable protection Position the LCD to be at typical eye level see Figure 1 Have clear access and viewing for brigade staff and operators Allow for the door to open at least 120 The MX1 must not be installed in hazardous areas as defined in AS NZS 3000 Fire Alarm System MX 1 1 m 1300 to 1850 mm Finish...

Page 3: ...Cabinet The 15U cabinet is supplied pre drilled with four keyholes suitable for mounting screws of not more than 8mm shaft diameter and 11mm head diameter A drilling template is supplied with each unit Refer Figure 2 b The keyhole detail is shown in Figure 2 c EXTERNAL WIRING Cable Entry Slimline Cabinet There are five 20mm knockouts provided in the top and five knockouts in the bottom of the cabi...

Page 4: ...ions on 15U cabinet Slimline Cabinet General Power Outlet current version A single switched GPO outlet is mounted on the right side of the cabinet and the power supply module is plugged into it See Figure 4 a The mains outlet is supplied with the MX1 and must be wired by a suitably qualified electrician to comply with NZ electricity safety regulations A dedicated current limited supply must be use...

Page 5: ... the earth wire from the terminal block to the GPO Figure 4 b 15U Cabinet Mains Wiring Battery Wiring The MX1 Slimline cabinet has space for a pair of 12V batteries up to 17Ah or 24Ah mounted on their sides These will be sufficient for most brigade connected systems The MX1 15U cabinet has space for a pair of 12V batteries up to 40Ah Many non brigade connected systems will require up to 40Ah batte...

Page 6: ... short circuits or overloads to a single zone FIRE DEF NC2 C2 NO2 MX1 CONTROLLER NC2 C2 NO2 AR BRIGADE SIGNALLING INTERFACE ASE 0V ASE INTERFACE Detector Detector Detector Detector Detector Detector Detector Module Module Detector AR AL AL Figure 6 Addressable Devices on MX Loop Note that the 850P 850PH 850PC and 850H detectors have built in short circuit isolators when fitted to 4B C bases Refer ...

Page 7: ...LM0459 and fuse provided with the T Gen2 This wiring provides complete supervision of wiring open and short circuits as well as passing the state of the T Gen2 s fault relay to the MX1 controller The 10k resistor is critical to this supervision and should not be omitted or a different value substituted ANC2 could be used to control the T Gen2 instead of ANC1 but this will require manual wiring as ...

Page 8: ...his supervision and should not be omitted or a different value substituted When the T GEN 50 Alert and Evacuation tones must be separately controlled by the MX1 one of the GP OUT terminals must be connected to the T GEN 50 s A I E input as shown This is not default operation and the MX1 must be specially configured Refer to the T GEN 50 Installation Manual LT0186 for information about its DIP swit...

Page 9: ...Figure 9 Wiring Ancillary Relay to Mini Gen s Multiple Branched Loads Ancillary relay ANC3 can supervise wiring to controlled loads on up to three branches This output can switch loads up to 5A resistive at 30V Figure 10 shows the necessary wiring The loads must all be isolated with diodes as shown in the figure A suitable diode for loads up to 1A each is 1N5404 Inductive loads such as bells must ...

Page 10: ...table Inductive loads such as door holders must have a suppression diode connected as shown A suitable diode is 1N5404 Note that ANC1 and ANC2 contacts are only rated at 1A inductive at 30V The MX1 must be configured to have the supervision input operate in door holder mode Normally energised loads EOLR EOLR EOLR values can be from 2k7 27k but must be the same value MX1 CONTROLLER ANC RELAY 1 ANC ...

Page 11: ... Wiring General Purpose Outputs SGD or Brigade Relay Interface The gear plate has plastic standoffs fitted to mount a GP SGD part number PA0862 or GP Brigade Relay Interface part number PA0861 in the top left part of the Slimline cabinet or on the top of the right hand gear plate return of the 15U gear plate The PA0861 or PA0862 is connected to the Brigade Signalling Interface connector on the Con...

Page 12: ...V TXRZDU RXRZDU V 0V RXRZDU 0V QE90 RDU 3 Line Powered RX 0V TX VRZDU Tx and Rx crossover between Master and first RDU Figure 16 Wiring to RZDU Devices ZONE LED DISPLAYS Rear Service Slimline Cabinet MX1 is supplied with one zone LED display board fitted on the gear plate in a rear service format as shown in Figure 16 Figure 17 Single Zone Display on gear plate Rear Service format A second zone di...

Page 13: ...tion One LM0092 cable will be needed to run from the LCD keyboard to the highest number zone LED board on the ME0457 and 1 x LM0056 will be needed to connect LED displays on one ME0457 to either the next or to the MX1 4U inner door An additional LM0056 will be needed when the second ME0457 is fitted Drawing 1982 88 shows example arrangements ZONE DISPLAY LABELLING Front Service Slimline 15U Cabine...

Page 14: ...mote Fire Brigade Panel RFBP The MX1 Remote FBP is powered by and communicates with the MX1 panel Installation and wiring of the RFBP is described in LT0545 supplied with each RFBP MX1 15U Cabinet Additional installation and wiring information is contained in the MX1 Au Fire Alarm System Wiring Diagrams LT0442 Note that some information in LT0442 is Australian specific MX1 Networking MX1 panels ca...

Page 15: ...d by one of the MX1 s VBF supplies This supply must not be used for any directly connected field wiring to ensure that fuse failure caused by an external wiring fault does not disable the network Alternatively the I HUB and fibre modems if included could be powered off the Loop Interface Supply terminals J33 using a fused power lead e g a spare LM0459 supplied with an MX Loop Card The I HUB s J4 T...

Page 16: ...screened cable may be increased to 1 500 meters Termination is detailed in Section 3 9 of the I HUB User Manual LT0229 I HUB Fibre Optic Ring Ports 1 and 2 can be combined to operate in a 2 wire ring arrangement with other I HUBs using fibre optic modems and fibre optic cable Fibre optic modems convert the RS485 signal interface into optical signals for transfer via optical cable Fibre optic trans...

Page 17: ...mounting plate and mount it on the standoffs using 8 screws as shown in Figure 25 Optional OSD fibre modems can be mounted on the gear plate or on the right hand side of the cabinet in place of the MX1 Loop Card using the FP1032 OSD139 Fibre Optic Modem Bracket see Figure 25 26 Note When using fibre cabling you must allow for cable entry and the minimum bend radius in deciding the cable route to t...

Page 18: ...ed lead e g a spare LM0459 supplied with an MX Loop Card The PIB s J24 serial port is connected using loom LM0576 to whichever serial port 0 2 3 or 4 is configured in the MX1 for networking Figure 29 PIB to MX1 Wiring To enable the PIB to be used to remotely access the MX1 for programming remote diagnostics or remote operation then a null modem serial cable LM0076 must be fitted between the PIB s ...

Page 19: ...ti mode fibre ports with SC connectors SU0320 MOXA 5 PORT E NET SW 2 SINGLE MODE FIBRE This switch has 3 Ethernet ports and 2 single mode fibre ports with SC connectors If shielded CAT3 5 6 copper Ethernet cable STP is being used to connect from one Moxa switch to the next 100m refer to the PIB User Manual LT0519 for installation and wiring details A Westermo Ethernet Extender module SU0328 may be...

Page 20: ...cally connected to the gearplate cabinet earth Figure 32 PIB Earthing Slimline Cabinet The PIB is mounted on the 5 plastic standoffs and 1 metal standoff on the left side of the gear plate as shown in Figure 33 An Earth loom must be connected between the J25 Earth tab top left on the PIB to the Earth stud on the left side of the cabinet A Moxa switch and one Ethernet extender or 2 Ethernet extende...

Page 21: ... 3 an earth lead will be required to be fitted between earth tab J25 and the gearplate No earth lead is required for J23 as there is a metal standoff on the gearplate A Moxa switch and one Ethernet extender or 2 Ethernet extenders can be mounted using one FP1012 mounting bracket This bracket is mounted on the left side of the gearplate as shown in Figure 35 Note the Moxa switch needs to be earthed...

Page 22: ...all Instructions LT0587 A copy of LT0587 is included with every FP1056 MX1 Fan Controls 3U 19 rack door and FP1057 MX1 Fan Controls expansion kit A generalized wiring arrangement is shown in Figure 36 Note The DIP switch on each fan control needs to be set to a unique odd number from 1 to 125 All controls must have their M switch set to ON except the one that connects to the MX1 Controller or MX L...

Page 23: ... software version number briefly before changing to the main MX1 system display Within 30 seconds the buzzer should sound Press SILENCE BUZZER on the keypad to stop the noise Press FAULTS and verify that a battery connection fault is displayed This may take up to 30 seconds Connect the battery The green BATT CONN LED on the controller should light unless the battery is very flat If this LED does n...

Page 24: ...y EOLRs 2 x 2 7k 1 x 9 1k 2 x 18k 3 x 27k 1 x 5 6k 1 x LT0344 MX1 Operator Manual 1 x LT0360 MX1 NZ Installation Guide 1 x LT0356 Inspection Checklist or LT0542 15U Checklist 1 x LM0319 TGEN Connection Loom 4 x M3 x 12mm screws for mounting optional Zone Display Board T GEN etc 1 x 003 key 4 x M5 screws nuts and washers for attaching battery leads to batteries Battery leads 1 x Red 1 x black 1 x r...

Page 25: ...ision ANC1 has a demountable screw terminal header compatible with pre made loom LM0319 to connect to a T Gen2 or T GEN 50 tone generator ANC2 has 2 5mm2 capacity screw terminals ANC3 A single set of voltage free changeover contacts 5A resistive at 30V Negative bias supervision of up to three branches of wiring is possible from this relay EOLR values are 9 1k for a single branch 2 x 18k for a doub...

Page 26: ...ion Guide MX1 Fire Alarm System NZ LT0360 ISSUE 2 43 29 NOVEMBER 2017 PAGE 26 Manufactured Johnson Controls by 17 Mary Muller Drive PO Box 19 545 Christchurch 8022 New Zealand Tel 64 3 389 5096 Fax 64 3 389 5938 ...

Reviews:

Related manuals for MX1