1.3 SPECIFICATIONS
1.3.1 GENERAL
Mains Supply:
240Vac @ 50Hz, +6% -10%, 100VA
(Not applicable to Rack Mounting model FP0533)
Power Supply/Charger:
27.3 Vdc* nominal at 20° C (Adjustable)
Rated Current:
Standard Models 1.5 Amps minimum (Typically 2.2 Amps)
High Power Models 6A nominal
Charger High Threshold:
28.15 + 0.25 Vdc*
Charger Low Threshold:
26.45 + 0.25 Vdc*
Battery Low Threshold:
24.10 + 0.25 Vdc*
* Temperature compensated, -36mV /
°
C
Battery Fail Threshold:
19.25 + 0.25 Vdc
Battery Requirements:
24V nominal, sealed lead acid, capacity to meet AS2220.2.
See Appendix A. Sizes up to 9.5Ah fit inside FP0530 cabinet.
Operating Temp:
-5
°
C to 45
°
C
Operating Humidity:
10% to 95% RH non-condensing
System Capacity:
1 Zone
Current Consumption:
All figures typical @ 27.3 Vdc
Standard Models, 25W output.
Quiescent (no BGM): 0.21A
Full Load (sinewave): 2.1A
Full Load (tones):
1.6A
No Load (tones):
0.45A
100W Amplifier fitted.
Quiescent (no BGM): 0.3A
Full Load (sinewave): 7A
Full Load (tones):
5A
No Load (tones):
0.8A
200W Amplifier fitted.
Quiescent (no BGM): 0.4A
Full Load (sinewave): 14A
Full Load (tones):
10A
No Load (tones):
1.3A
Note : Any strobe or auxiliary load currents must be added to
the above figures.