TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page
24
of
26
RESET
key is user password protected. System reset action is under user password protection. User can reset and
restart the system any time. Basically the zone fire condition is latched in the system, user can perform required
action for this condition. To recover the system from zone fire condition to zone normal condition, user must reset
the System, LCD displays as shown below.
4.1.4 Enter Key
This key use for save configuration changes as well as jump in to next menu function. Following are two main use
of this key for user,
a.
Access the new menu
b.
Saves configured data, mode or value of the system
4.2 Normal Mode Operation
This section explains the system behaviour under different conditions. The System continuously monitors for fire
and system faults in all modes of operation.
When system is power ON,
System ON
LED is continuously ON. LCD displays show below screen,
If panel mains is not available panel will sifted in battery mode as well as MAINS FAIL led will also glow for
notification to user.
TrueSafe
SYSTEM OK
4.2.1 Fire Condition
If any zone detects the fire, the system enters immediately into fire condition.
The System operation and LCD display for this condition is shown below. As well as respective LED will also glow.
•
First one lines indicate Zones in Fire, 2nd line indicates type of event occurred in system like Fire or fault.
•
The zone fire status is visually indicated by respective zone fire LED.
•
Common Twin Fire LED turns ON.
•
Internal buzzer produces steady sound for fire indication.
Zone 1 Fire
ALARM [1/1]
Panel
RESETTING……..