TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page
12
of
26
2.3 Panel Wiring
The following diagram shows basic components of Fire Panel System. It consists of various smoke and heat
detectors, AC power source, Notification devices like siren or sounder, etc
WARNING
:
Several different sources of power can be connected to this panel. Disconnect all sources of power before
servicing. The panel and associated equipment may be damaged by removing and / or inserting cards, modules
or inter connecting while this unit is energized.
Primary Power source (AC) and Earth Ground Connection
:
AC Power connections are made inside the control panel cabinet. A separate Earth Ground connection must be
made to ensure the proper panel operation and lightening and transient protection.
Standby Power Source (Batteries)
:
Use one 24V/1.2Ah sealed lead acid type Battery. Observe polarity when connecting the battery. Connect the
battery to the provided cable. The battery charger is current - limited and capable of recharging sealed lead acid
type batteries up to 8Ah.
Display
Keypad
Zone 1
Zone 4
Two/Four IDC
3 PFC Output
2 for Fire
1 for Fault
1 NAC
(Siren Output-500mA)
TSFC 24-2/4 Panel
WiFi
Connectivity
230VAC/50Hz
Supply With
Battery Backup