1.4.3 LCD Indication
The 16 x 2 Large LCD display is used in TSFC panel to display different system fault status, zone fire status,
configuration menus & so on. The LCD is mainly used Fire indications and for the programming of the panel listed
as below.
•
Fire Indications
•
Fault Indications
•
Zone modes
•
View history events
•
Panel Configuration setting
•
Change user / admin password
1.4.4 Buzzer Indication
A buzzer provides separate and distinct sounds for Fire, Faults and Walk Test Fire.
•
Fire: Continuous Buzzer ON.
•
Fault: 1 sec ON and 5 sec OFF.
•
Walk Test Fire: 1 sec ON and 1 sec OFF.
1.5 Components
EOL Resistor
:
•
4.7K ohm 1 W Resistor is connected in parallel with each input zone for zone open/short/fire sensing purpose.
Hence 2 resistors are required for TSFC 24-2 & 4 resistors are require for TSFC24-4 model.
•
4.7K ohm 1 W Resistor is connected in parallel with NAC output
9
Zone Fire
Red
If zone in fire condition, ON
10
Zone Fault/WT
Yellow
If zone in Fault/WT Mode, ON
11
Zone Bypass
Yellow
If zone disable, ON