5693 982 - 04
Vitotronic 300, GW2B Installation and Service
Installation Sequence
CAUTION
The control must be grounded. Ensure that “L”, “N” and
“G” are not interchanged.
1. Ensure that the main power supply to the control
contains overcurrent protection with a maximum
rating of 15A and 2 pole disconnect.
2. Connect power supply wire to the Connection
fÖ
terminals 11, N and G on the DIN rail inside the
connection
enclosure.
Burner Connection, Motor Power Supply
Supply power must be sufficient to cover both the 12A
control plus the required motor amperage.
Legend
A
Burner motor power supply 120VAC, 1PH
B
Connection terminals and plug inside
connection
enclosure
C
Cable and conduit- factory supplied
D
Burner
E
Motor starter
F
Burner motor
G
Connection enclosure on boiler control