Checking the connection on the flue gas side for leaks
B
C
A
Note
Traces of condensate indicate a leak.
1.
Remove thermal insulation hood
A
.
2.
Remove thermal insulation strip
B
and pull thermal insulation mat
C
out a little.
3.
Check the heat exchanger fixings for
firm seating.
4.
Check all sealing points on the heat
exchanger, boiler flue connection
and flue system.
Commissioning, inspection, maintenance