29
Gas boiler, category I
2ELL
Rated heating output
kW
125
160
195
230
270
Product ID
in accordance with the Efficien-
cy Directive
CE-0085BS0005
Pressure drop on the hot gas
side
Pa
65
95
100
120
160
mbar
0.65
0.95
1.00
1.20
1.60
Required draught
Pa/mbar
0
0
0
0
0
Flue gas parameters
Temperature
*3
at boiler water
temp. 60 °C
■ At rated heating output
°C
175
■ At partial load
°C
125
Temperature
*3
at boiler water
temp. 80 °C
°C
185
Product parameters
(according to EnEV)
Efficiency η
at
■ 100 % of rated heating output
%
92.4
92.5
92.7
92.8
92.8
■ 30 % of rated heating output
%
95.2
94.9
95.5
95.6
95.6
Standby loss q
B,70
%
0.40
0.38
0.28
0.25
0.25
Power consumption
*4
at
■ 100 % of rated heating output
W
457
514
565
612
661
■ 30 % of rated heating output
W
152
171
188
204
220
*3
Flue gas temperatures as actual gross values at 20 °C combustion air temperature.
*4
Standard parameter.
Specification
Specification
5692 726 GB