Recommended minimum clearances
c
o2
f
o4/2
d
e
a
C
D
A
B
b
o4
Fig. 2
A
Boiler
B
Burner
C
Regulating and control system
D
Anti-vibration boiler supports
(option)
a
Control panel not fitted
b
Control panel depth
c
Control panel fitted
d,e,f
Remaining clearances
o2, o4 Max. length, max. width
Tab. 1
a/b/c
mm
≥1000/≥500/≥800
d/e/f
*1
mm
≥500/≥300/≥500
Observe the given dimensions to
ensure
easy installation and maintenance
.
Level the boiler horizontally.
Observe
risk warning
in chapter "Handling the
boiler".
We recommend
you position the boiler onto anti-vibration
boiler supports. For this, distribute sup-
ports evenly over the length and centrally
underneath the base rails. Observe the
information provided.
Tab. 2
Boiler size
1
2
3
4
5
6
o2
mm
6516
7056
7596
8116
8656
9416
o4
mm
2670
2840
2985
3200
3475
3650
*1
We recommend: Leave one boiler length (o2) of space clear in front of
the boiler door to facilitate the extraction of turbulators (if fitted) and cleaning.
Handling and siting the boiler