Fitting a flue pipe
ØD
Ø10
2-3xØD
Fig. 4
1.
Connect the flue outlet with the flue
system using a flue pipe with favour-
able flow characteristics.
2.
Locate the test port (approx. 10 mm
7
) at a distance of two to three times
the diameter of the flue pipe down-
stream of the flue outlet.
3.
Seal flue pipe.
4.
Insulate the flue pipe.
Optional
Flue gas flange with mating flange.
Tab. 3 - Flue outlet D
*2
Boiler size
1
2
3
4
5
6
D
7
mm
700
800
850
950
1000
1100
Note
■ Prevent the return of condensate cre-
ated inside the flue system by suitable
on-site measures (condensate trap).
■ Close the condensate drain connec-
tors if they are not used. They are
designed to drain any condensate col-
lected in the start-up phase.
Note
Connect all flue pipes free of load and
torque stress. Flue pipe joints must be
gas-tight.
*2
Internal diameter, for external diameter: + 10 mm
Connecting the flue gas side
(cont.)
5727 521 GB