Boiler size
1
2
3
4
5
6
7
8
9
A
total with ECO 100
m
3
11.3
13.5
15.1
17.7
18.4
22.0
25.9
31.0
39.2
45.0
total with ECO 200
m
3
11.3
13.5
15.1
17.7
18.5
22.1
26.0
31.2
39.3
45.2
average operating range
*4
with ECO 100
m
3
9.89 11.53 12.89 15.15 15.75 18.59 21.89 23.29 32.53
36.70
average operating range
*4
with ECO 200
m
3
9.94 11.59 12.96 15.22 15.84 18.68 22.03 26.44 32.72
36.87
Steam chamber volume
*4
m
3
1.38
1.94
2.18
2.53
2.64
3.41
4.02
4.75
6.62
8.29
Steam level surface area
*4
m
2
6.58
7.78
8.44
9.28
9.72 11.29 12.53 14.19 17.42
19.95
Boiler connections
Steam connector
for permissible operating pres-
sure
6 bar PN 16 DN
200
200
200
250
250
250
300
300
350
400
8 bar PN 16 DN
150
200
200
200
200
250
250
300
300
350
10 bar PN 16 DN
150
150
150
200
200
200
250
250
300
300
13 bar PN 40 DN
125
150
150
150
–
–
–
–
–
–
13 bar PN 25 DN
–
–
–
–
200
200
200
250
250
250
16 bar PN 40 DN
125
125
150
150
150
–
–
–
–
–
16 bar PN 25 DN
–
–
–
–
–
200
200
200
250
250
18 bar PN 40 DN
125
125
125
150
150
–
–
–
–
–
18 bar PN 25 DN
–
–
–
–
–
200
200
200
200
250
20 bar PN 40 DN
125
125
125
150
150
200
200
200
–
–
22 bar PN 40 DN
100
125
125
125
150
150
150
–
–
–
25 bar PN 40 DN
100
100
125
125
125
150
–
–
–
–
Safety valve connector
for permissible operating pres-
sure
6 bar PN 40 DN
65
65
65
80
80
100
100
100
125
150
8 bar PN 40 DN
50
65
65
65
80
80
100
100
100
125
10 bar PN 40 DN
50
50
65
65
65
80
80
80
100
100
13 bar PN 40 DN
40
50
50
65
65
65
65
80
80
100
16 bar PN 40 DN
40
40
50
50
50
65
65
65
80
80
18 bar PN 40 DN
40
40
40
50
50
65
65
65
80
80
20 bar PN 40 DN
32
40
40
50
50
50
65
65
–
–
22 bar PN 40 DN
32
40
40
40
50
50
65
–
–
–
25 bar PN 40 DN
32
32
40
40
50
50
–
–
–
–
Connector for feedwater pumps
PN 40 DN
40
40
40
50
50
50
65
65
65
80
Flue gas mass flow rate
- for natural gas
t/h
1.5225 x combustion output in MW
- for fuel oil EL
t/h
1.5 x combustion output in MW
Flue gas volume
- with ECO 100
m
3
6.4
8.0
9.3
10.7
12.4
15.0
18.4
23.4
30.6
35.1
- with ECO 200
m
3
6.5
8.2
9.5
10.9
12.5
15.0
18.6
23.8
31.0
35.5
*4
Average water level between pump ON and pump OFF.
Specification
(cont.)
6
VIESMANN
VITOMAX 200-HS
5442 026 GB
Summary of Contents for VITOMAX 200-HS
Page 150: ...150 VIESMANN VITOMAX 200 HS...