Set-up
11
Minimum Clearances to Combustibles
For typical installations, Viessmann recommends installing the boiler with
clearances as published on page 10 under Recommended Minimum Clearances for
Service.
Standard installation
(top view)
Boiler Model
VB2
-18
-22
-33
-40
-50
-63
Rear
inches
mm
6
150
6
150
6
150
6
150
6
150
6
150
Sides
inches
mm
0
0
0
0
0
0
0
0
0
0
0
0
Flue
(oil)
inches
mm
9
230
9
230
9
230
9
230
9
230
9
230
(gas)
inches
mm
6
150
6
150
6
150
6
150
6
150
6
150
Alcove installation
(side view)
Boiler Model
VB2
-18
-22
-33
-40
-50
-63
Rear
inches
mm
6
150
6
150
6
150
6
150
6
150
6
150
Sides
inches
mm
0
0
0
0
0
0
0
0
0
0
0
0
Flue
(oil)
inches
mm
9
230
9
230
9
230
9
230
9
230
9
230
(gas)
inches
mm
6
150
6
150
6
150
6
150
6
150
6
150
Top
inches
mm
6
150
6
150
6
150
6
150
6
150
6
150
Front
(AL)
inches
mm
6
150
6
150
6
150
6
150
6
150
6
150
*
Viessmann strongly recommends maintaining 48” / 1200 mm front clearance on all models.
5167
404
v1
.9
min. 6”
150 mm
min. 0” / 0 mm
service
clearance
48”
1220 mm*
min. 6” / 150 mm
service
clearance
48”
1220 mm*
gas:
min. 6” / 150 mm
oil:
min. 9” / 230 mm
min. 6” / 150 mm