Set temperature
B
Start hysteresis
C
Heating the heating water buffer cyl-
inder OFF
D
Heating the heating water buffer cyl-
inder ON
Menu
■
"Device settings"
■
"Programming"
■
"Buffer cylinder"
■
"Hysteresis"
Delivered condition
5 K
Setting
2 to 20 K
Maximum temperature
Upper temperature limit for the heating
water buffer cylinder.
Heating of the heating water buffer cyl-
inder ends when this temperature is
reached.
Note
■ This function is only available for sys-
tem schemes 1 and 2 if the option
"Yes" was selected under "Buffer
cylinder".
■ If the value specified here is below the
maximum possible set flow tempera-
ture of one of the connected heating
circuits, this heating circuit may not be
able to be supplied with the calculated
flow temperature when there is a
greater heat demand.
Menu
■
"Device settings"
■
"Programming"
■
"DHW"
■
"Max. temperature"
Delivered condition
60 °C
Setting
1 to 70 °C
Control settings, heating water buffer cylinder
Hysteresis
(cont.)
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...