157
Note
While the compressor is running, the
control unit in this overview displays the
current test values. After the compressor
has shut down, the last values measured
during operation can be called up. These
values are only overwritten when the
compressor starts again.
Heat pump
BACK
2
2
H
Err / Msg : 00000001 00000000
1
tpe
tpa
tse
tsa
p0
pc bara :
bara :
°C :
°C :
°C :
°C :
1
14.1
6.2
31.5
22.2
11.3
19.8
0.0
0.0
0.0
Displays
Display
Explanation
tpe °C
Air intake temperature
tpa °C
Air discharge temperature
tse °C
Secondary circuit return temperature
tsa °C
Secondary circuit flow temperature
p0 bara
Evaporation pressure
pc bara
Condensation pressure
Err/Msg
Last fault information code before a compressor shutdown; display
system (see page 153) and explanation (see page 155) as before.
Hours run according to load classes
The compressor hours run given in the individual lines belong to the load classes
shown below. Column
"1"
shows the values for the heat pump, column
"2"
has no
function.
Heat pump
BACK
2
2
1
1.
h :
1
2.
3.
4.
5.
h :
h :
h :
h :
RESET
T/P
0
00
0
0
0
0
644
0
0
671
Load class
Hours run for ΔT
V/K
1
ΔT
V/K
< 25 K
2
25 K < ΔT
V/K
< 32 K
3
32 K < ΔT
V/K
< 41 K
4
41 K < ΔT
V/K
< 50 K
5
ΔT
V/K
> 50 K
ΔT
V/K
Differential, evaporation and con-
densation temperature
Troubleshooting
Control unit diagnostics
(cont.)
5414 828 GB
Service
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...