57
External hook-up for heating/cooling circuits
Parameter
Setting
"Heating circuit 1"
/
"Heating circuit 2"
/
"Heating circuit 3"
Ó
"Remote control 2003"
or
"Remote control 3003"
or
"Remote control 4003"
"2"
Cooling function parameters
Parameter
Setting
"Cooling"
Ó
"Cooling function 7100"
"0"
No cooling
"1"
Natural cooling with NC-Box with-
out mixer (accessories)
"2"
Natural cooling with NC-Box with
mixer (accessories)
"3"
Never adjust.
"Cooling circuit 7101"
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"3"
Heating circuit M3/HC3
"4"
Separate cooling circuit SKK
Room temperature sensor for separate cooling circuit
Parameter
Setting
"Cooling"
Ó
"Ranking room temp sensor separate cooling circuit 7106"
"0"
Connection F16
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"3"
Heating circuit M3/HC3
"4"
Never adjust.
Parameters for solar DHW heating
Parameters in conjunction with solar control module type SM1
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"3"
Parameter C0xx
See installation and service instruc-
tions for "Solar control module, type
SM1".
Parameters for instantaneous heating water heater
Parameter
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater 7900"
"1"
"Output for instant. heating water heater at power-OFF 790A" "1"
3 kW
"2"
6 kW
"3"
9 kW
Commissioning, inspection, maintenance
Commissioning the system
(cont.)