27
Rated heating output
kW
90
115
140
180
235
300
405
500
Rated heat input
kW
97
124
151
194
254
323
436
538
Permiss. flow temperature
(= safety temperature)
°C
110 (up to 120 °C on request)
Permiss. operating pres-
sure
bar
4
kPa
400
Pressure drop on the hot
gas side
Pa
40
60
80
100
200
200
250
330
mbar
0.4
0.6
0.8
1.0
2.0
2.0
2.5
3.3
Boiler body dimensions
Length excl. boiler door
mm
1215
1420
1405
1600
1820
1820
1865
2010
Width
mm
575
575
650
650
730
730
865
865
Height (incl. connectors)
mm
1145
1145
1180
1180
1285
1285
1455
1455
Overall dimensions
Length excl. burner
mm
1300
1500
1485
1680
1905
1905
1945
2090
Length incl. burner and hood mm
1700
1905
1910
2110
2330
2330
–
–
Width
mm
755
755
825
825
905
905
1040
1040
Height incl. control unit
mm
1315
1315
1350
1350
1460
1460
1625
1625
Maintenance height (control
unit)
mm
1485
1485
1520
1520
1630
1630
1795
1795
Foundation
Length
mm
1000
1200
1200
1400
1650
1650
1650
1800
Width
mm
760
760
830
830
900
900
1040
1040
Combustion chamber di-
ameter
mm
380
380
400
400
480
480
570
570
Combustion chamber
length
mm
800
1000
1000
1200
1400
1400
1400
1550
Weight
Boiler body
kg
350
394
460
490
650
742
940
1110
Weight incl. thermal insula-
tion and boiler control unit
kg
395
440
510
540
710
802
1075
1295
Weight incl. thermal insula-
tion, boiler control unit and
burner
kg
420
464
540
570
740
832
–
–
Capacity
boiler water
litres
170
210
250
290
470
430
590
630
Boiler connections
Boiler flow and return
PN 6
DN
65
65
65
65
65
80
100
100
Safety connection
(safety valve)
R
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
1
½
1
½
Drain
R
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
Flue gas parameters
*2
Temperature (at 60 °C boiler
water temperature)
–
At rated heating output
°C
160
–
At partial load
°C
105
*2
Values for calculating the size of the flue system to EN 13384, relative to 13 % CO
2
for fuel oil EL and 10 % CO
2
for natural
gas.
Flue gas temperatures as actual gross values at 20 °C combustion air temperature.
The details for partial load refer to an output of 60 % of rated heating output. If the partial load differs (depending on operat-
ing mode), calculate the flue gas mass flow rate accordingly.
Specification
Specification
5692818
Appendix