The controller compares the temperature at sensor
S1 to the temperatures at sensors S2, S4 and S5. If the
measured temperature differences are higher than the
adjusted switch-on temperature differences, the pump
(R1, R2 and/or R3) will be activated and the corre-
sponding tank will be loaded up to the adjusted maxi-
mum temperature at most. Priority loading or parallel
loading can be carried out in this system.
System 6
3-tank solar system with pump logic and priority logic
Sensor/
terminal
Designation
Description
S1
TCOL
Temperature collector
S2
TST1B
Temperature tank 1 bottom
S3
Optional sensor for measure-
ment purposes or options
S4
TST2B
Temperature tank 2 bottom
S5
TST3B
Temperature tank 3 bottom
V40
Optional sensor for measure-
ment purposes or options
Relay
Description
R1
Solar pump tank 1
R2
Solar pump tank 2
R3
Solar pump tank 3
R4
optional:
Thermal disinfection
Parallel relay
Heat dump