10
5285 280 v1.0
Cascade System Guide
Set-up for Cascade System with Vitocontrol-S
Preparing the single boiler connections to the pump power module and the coding addresses that needs to be changed.
Require coding changes for the Vitotronic 100 HC1 boiler
control (changes to be made in Coding 2):
- coding address 01:1 changed to 01: 2
(multiple boiler systems)
- coding address 07: changed to 07:_(for each boiler #
in the cascade system)
- coding address 76:0 changed to 76:2
(with cascade communication module)
- coding address 77: changed to 77:_(for each boiler #
in the cascade system)