Pyrotec Technical Data
Technical Data
Boiler model KPT-
390
530
720
950
1250
Maximum output
MBH (kW)
1331 (390)
1808 (530)
2457 (720)
3242 (950)
4265 (1250)
Minimum output
1
MBH (kW)
334 (98)
450 (132)
614 (180)
812 (238)
1065 (312)
Efficiency
2
85%
Fuel Moisture content
3
%
W 50
Size of wood chips
4
G 30 / G 50 as per CAN/CSA-B366. 1-M91
Flue gas figures
Connection flue gas pipe
7
A
Mass flow rate; W5; O
2
6%
Volume flow; W5; O
2
6%; 302°F (150ºC)
Mass flow rate; W35; O
2
8%;
Volume flow;W35; O
2
8%; 302°F (150ºC)
Average flue gas temperature at full load
5
Average flue gas temperature at partial load
5
Chimney draft required
in. mm
lb/s (g/s)
ft³/s (m³/s)
lb/s (g/s)
ft³/s (m³/s)
°F (°C)
°F (°C)
Pa
13
b
(350)
0.48 (219)
9.18 (0.26)
0.67 (303)
13 (0.37)
13
c
(350)
0.65 (297)
12.71 (0.36)
0.91 (412)
17.5 (0.50)
13
c
(350)
0.89 (404)
17 (0.48)
1.23 (560)
23.6 (0.67)
15
c
(400)
1.17 (532)
22 (0.63)
1.62 (736)
31 (0.88)
17
c
(450)
1.54 (700)
29 (0.83)
2.13 (968)
40.6 (1.15)
320 (160)
248 (120)
±0
Electrical connections
Electrical connections, total
Ignition device
Flue gas blower
In-feed auger
Primary air flow blower
1
Primary air flow blower
2
Secondary air flow blower
Grate drive unit
Electric power consumption at full load
Electric power consumption at partial load
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
6.42
1.6
1.5
1.1
0.14
1.0
.9
0.12
3.36
2.75
8.28
1.6
2.2
1.5
0.3
1.0
1.5
0.12
4.68
3.83
8.28
1.6
2.2
1.5
0.3
1.0
1.5
0.12
4.68
3.83
9.51
1.6
2.2
2.2
0.48
1.0
1.85
0.12
5.29
4.28
11.31
1.6
4.0
2.2
0.48
1.0
1.85
0.12
6.91
5.6
Heating
Water side resistance (diff. 27° F / 15 K)
Boiler water volume
Heating surface
Volume on heating gas side
Volume of ash container for grate ash
Volume of ash container for flue gas de-duster
Test pressure
6
Maximum allowable working pressure (water)
6
Maximum water temperature
Minimum return temperature
“wc (mbar)
USG (L)
ft² (m²)
USG (L)
USG (L)
USG (L)
psi (bar)
psi (bar)
°F (°C)
°F (°C)
5.12 (13)
303 (1150)
291.8 (27.1)
407 (1540)
9.23 (23)
383 (1450)
457.5 (42.5)
602 (2280)
17.26 (43)
488 (1850)
597.4 (55.5)
774 (2830)
10.5 (26)
515 (1950)
805.2 (74.8)
1070 (4050)
18 (45)
660 (2500)
979.6 (91.0)
1367 (5210)
63 (221) - 240 (800)
63 (221) - 240 (800)
113 (7.8)
30 or 60 (2 or 4)
250 (120)
149 (65)
Weight
Weight of fire box
Weight of pressure vessel (30 psi)
Weight of pressure vessel (60 psi)
Weight of displacement rods
Weight of flue gas blower
Weight of in-feed auger
Total weight without water (30psi)
7
Total weight without water (60psi)
7
Total weight with water (30psi)
7
Total weight with water (60psi)
7
lb (kg)
lb (kg)
lb (kg)
lb (kg)
lb (kg)
lb (kg)
lb (kg)
lb (kg)
lb (kg)
lb (kg)
6570 (2970)
4993 (2265)
4993 (2265)
644 (292)
132 (60)
337 (153)
12820(5815)
12820(5815)
15355(6965)
15355(6965)
9343 (4238)
7094 (3218)
7094 (3218)
721 (327)
172 (78)
337 (153)
17780(8065)
17780(8065)
20964(9509)
20964(9509)
10919 (4953)
9275 (4207)
9936 (4507)
869 (394)
178 (78)
3.37 (153)
21572(9785)
22234(10085)
25675(11646)
26336(11946)
12740(5779)
12965 (5881)
13627 (6181)
1186 (538)
181 (82)
419 (190)
27492(12470)
28153(12770)
31775(14413)
32437(14713)
14374(6520)
14643 (6642)
15525 (7042)
1186 (538)
236 (107)
419 (190)
30858(13997)
31740(14397)
36330(16479)
37212(16879)
1
Minimum load:
Operation with modulated control (Infinitely variable power control)
Low load with ON Qmin / OFF (Stop-and-go mode)
2
Moist fuels:
Efficiency: Specification with displacement rods and flue gas recirculation system
or dry fuels (W5 to W20) without flue gas recirculation system-reduced values
3
Wet fuels:
>W35 further limitations regarding output, degree of efficiency and control behavior
4
Specification:
See Section Wood Fuel Requirements
5
Flue gas temperature:
An increase is possible by removing the displacement rods [Full load 86° F (30° C);
Partial load 50° F (10° C)]
6
Pressure:
Per ASME Sec. IV
7
Overall weight:
Includes displacement rods
Other influences:
Fuel, water content, ash content, pneumatic cleaning system yes/no; track time (number of
operating hours without cleaning). Specifications for the start of the track time [toward the end
of the track time there is an increase in the flue gas temperature by approx. 59° F (15° C).
Mechanical