16
Initial start-up, inspection and maintenance
Further details of the individual steps
(cont.)
Cleaning and reconnecting the condensate drain
¨
ĂSafety instructions
Clean the inside of the drain pipe at least annually
.
The condensate drain, stench trap, neutralising system and all intermediate
hoses and pipes are part of the condensate drain system.
1.
Remove drain hoseĂ
G
to the drain
from condensate drain
connectionĂ
F
.
2.
Clean the inside of condensate
drainĂ
F
again
with a plastic
brush.
3.
Unscrew and flush bottom partĂ
P
of stench trapĂ
E
, and clean the
inlet connection of stench trapĂ
E
with a brush.
4.
Mount stench trap plugĂ
E
Ăon
condensate drainĂ
F
Ăand seal in if
necessary.
5.
Fill bottom partĂ
P
of the stench
trap with water and fit to the
stench trap.
¨
Ă
Safety instructions
There is a risk of flue gas escaping
if the stench trap is not filled with
water.
6.
Clean the inside of the condensate
drain and the neutralising system.
Neutralising system
operating instructions
7.
Replace the spent neutralising
agent.
Neutralising system
operating instructions
5692Ă480ĂGB