17
Permissible CO
2
content
Gas type
CO
2
con-
tent
Rated heating output in kW
at
87
115
142
186
246
311
Natural gas
E
Upper heat-
ing output
(100 %)
7.1 - 10.2 % 7.0 - 10.1 % 7.0 - 10.1 % 7.1 - 10.2 % 7.1 - 10.2 %
7.1 - 10.2 %
Actual value at upper heating output
minus
Lower heat-
ing output
(0 %)
0.3 - 0.7 %
0.3 - 0.7 %
0.3 - 0.7 %
0.4 - 0.8 %
0.4 - 0.8 %
0.4 - 0.8 %
Natural gas
H
Upper heat-
ing output
(100 %)
8.0 - 10.2 % 7.9 - 10.1 % 7.9 - 10.1 % 8.0 - 10.2 % 8.0 - 10.2 %
8.0 - 10.2 %
Actual value at upper heating output
minus
Lower heat-
ing output
(0 %)
0.3 - 0.7 %
0.3 - 0.7 %
0.3 - 0.7 %
0.4 - 0.8 %
0.4 - 0.8 %
0.4 - 0.8 %
Natural gas
LL
Upper heat-
ing output
(100 %)
7.2 - 10.0 %
7.1 - 9.9 %
7.1 - 9.9 % 7.2 - 10.0 % 7.2 - 10.0 %
7.2 - 10.0 %
Actual value at upper heating output
minus
Lower heat-
ing output
(0 %)
0.3 - 0.7 %
0.3 - 0.7 %
0.3 - 0.7 %
0.4 - 0.8 %
0.4 - 0.8 %
0.4 - 0.8 %
Natural gas
L
Upper heat-
ing output
(100 %)
8.3 - 10.0 %
8.2 - 9.9 %
8.2 - 9.9 % 8.3 - 10.0 % 8.3 - 10.0 %
8.3 - 10.0 %
Actual value at upper heating output
minus
Lower heat-
ing output
(0 %)
0.3 - 0.7 %
0.3 - 0.7 %
0.3 - 0.7 %
0.4 - 0.8 %
0.4 - 0.8 %
0.4 - 0.8 %
CO
2
test at the upper heating output (87 kW)
Fig. 10
1.
Press until the service display has counted up to
"100" (= 100 %).
2.
Check the CO
2
content at the flue pipe.
For permissible CO
2
content, see above table.
3.
Check control cables:
■
Connection and kink-free routing
■
Application and seating of retaining clips
Note
The unconnected end of the hose is open in open
flue operation. For
room sealed
operation, the end
of the hose is pushed onto the intake adaptor.
Commissioning, inspection, maintenance
Checking the CO
2
content
(cont.)