80
4.
Check the CO
2
content. Should the
actual value deviate from the above
ranges, implement steps from page
79.
5.
Record the actual value on
page 184 of the commissioning/
service report.
6.
Adjust
"Eng + Supp bu max"
(see
page 80).
7.
Check the CO
2
content. Should the
actual value deviate from the above
ranges, implement steps from page
79.
8.
After testing, press
d
.
9.
Record the actual value on
page 184 of the commissioning/
service report.
Setting the heating output
1.
If necessary, press "ESC" repeat-
edly, until the default display is
shown.
2.
Press "
Ð
"; this activates the emis-
sions test function (see page 160).
3.
Press "OK".
"Eng burner min"
flashes on the dis-
play.
4.
Select the individual output settings
with rotary selector "
J
":
■
"Eng burner min"
(Stirling burner
minimum)
■
"Eng + Supp bu max"
(Stirling &
auxiliary burner max)
5.
Confirm with "OK".
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5618 294 GB