186
Rated voltage
230 V
Rated frequency
50 Hz
Rated current
6 A
Safety category
I
IP rating
IP X 4 D to
EN 60529
Permissible ambient temperature
■ during operation
0 to +40 °C
■ during storage and
transport
-20 to +65 °C
Electronic tempera-
ture limiter setting
82 °C
Temperature limiter
setting
100 °C (fixed)
Backup fuse (power
supply)
max. 16 A
Gas condensing boiler I
2ELL
Rated heating output range
T
V
/T
R
40/30 °C
kW
3.5 to 26
Rated heating output range
T
V
/T
R
75/60 °C
kW
3.2 to 24.6
Rated heat input range
kW
3.6 to 25.2
Nominal electrical rating (max.)
kW
1.0
Total elect. consumers (max.)
W
138
Connection values
relative to the max. load
Natural gas E
m
3
/h
2.61
Natural gas LL
m
3
/h
3.11
Product ID
_
-0085CM0150
Note
The connection values are only for doc-
umentation purposes (e.g. in the gas
contract application) or to estimate a
supplementary volumetric settings
check. Due to the factory settings, the
gas pressure must not be altered from
these values. Reference: 15 °C,
1013 mbar.
Specification
Specification
5618 294 GB
Summary of Contents for C3HA
Page 39: ...39 2 2x 1 Installation sequence Removing the front panel 5618 294 GB Installation ...
Page 42: ...42 1 2 Installation sequence Removing the transport brackets 5618 294 GB ...
Page 151: ...151 Checking and replacing resistors B C A Troubleshooting Repairs cont 5618 294 GB Service ...
Page 181: ...181 Parts lists Control unit assembly cont 5618 294 GB Service ...
Page 183: ...183 Parts lists Miscellaneous assembly cont 5618 294 GB Service ...