94
Vitocal 300-G, type BW 301.C17
Performance data
to EN 14511 (B0/W35, 5 K spread)
Rated heating output
kW
18.33
Refrigerating capacity
kW
14.57
Power consumption
kW
4.11
Coefficient of performance
ε
(COP)
4.47
Brine
(primary circuit)
Capacity
l
5.9
Minimum flow rate
l/h
2600
Pressure drop at minimum flow rate
mbar
50
kPa
5
Max. flow temperature (brine inlet)
°C
15
Min. flow temperature (brine inlet)
°C
–
10
Heating water
(secondary circuit)
Capacity
l
3.8
Minimum flow rate
l/h
1600
Pressure drop at minimum flow rate
mbar
34
kPa
3.4
Max. flow temperature
°C
50
Electrical values, heat pump
Compressor rated voltage
3/N/PE 400 V/50 Hz
Compressor rated current
A
15.9
Compressor starting current
A
75.0
Starting current, compressor with stalled armature
A
102.0
Compressor fuse protection
A
C16
3-pole
Protection class
I
Electrical values, heat pump control unit
Rated voltage
1/N/PE 230 V/50 Hz
Fuse protection
B16A
Fuses
2 x 6.3 A H (slow)/250 V
Max. power consumption
W
1000
Power consumption in operation
W
5
Refrigerant circuit
Refrigerant
R290
■
Refrigerant charge
kg
1.2
■
Global warming potential (GWP)
3
■
CO
2
equivalent
t
0.0036
Max. permissible pressure
■
Low pressure
bar
17
MPa
1.7
■
High pressure
bar
26
MPa
2.6
Compressor
Type
Hermetically sealed scroll
■
Oil in compressor
Type
Hatcol 4467
■
Quantity of oil in compressor
l
1.9
Specification
Specification
5800 917 GB
Service