58
Parameters for external heat source
Parameters
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
Enable external heat source for DHW heating
"External heat source"
Ó
"Enable external heat source for DHW heating 7B0D"
"1"
Release circulation pump for DHW reheating
"External heat source"
Ó
"Enable booster heaters for DHW heating 6014"
"1"
Parameters for swimming pool water heating
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"Swimming pool 7008"
"1"
Parameters for solar DHW heating
Parameters in conjunction with solar control module type SM1
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"3"
Parameter C0xx
See installation and service instruc-
tions for "Solar control module, type
SM1".
Cooling function
Cooling function parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
"0"
No cooling
"1"
Natural cooling with NC-Box without mix-
er (accessory)
"2"
Natural cooling with NC-Box with mixer
(accessory)
"3"
"Active cooling"
"Cooling"
Ó
"Cooling circuit 7101"
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"3"
Heating circuit M3/HC3
"4"
Separate cooling circuit SKK
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5787 232 GB