Subject to changes due to technical improvements
ESS Energie Systeme & Service GmbH
32
CHP accessory range – 01/2010
5368 463
Electronics
6
Optional versions
• OPTION MMM Additional auxiliary drive
and functions
Fuse outlet 230 V / 16 A (e.g. for boiler) incl. installation
Please note: a separate control panel extension is required for this option!
• OPTION MMM Additional auxiliary drive
Pump control up to 4 kW
Please note:
a separate control panel extension is required for this option!
• OPTION MMM Databus connection LON BUS
alternative
OPTION MMM Databus connection ProfiBus DP slave
alternative
OPTION MMM Databus connection CANopen BUS
alternative
OPTION MMM Databus connection MODBUS BUS
Computer connection in each case according to requirements on site
• OPTION MMM Remote monitoring / actual data capture with Telecontrol "Exclusive"
Remote monitoring and actual data capture takes place via an external appliance, the so-called
Telecontrol. The Telecontrol is connected to the MMM via a serial interface. Using the associated
visualisation software, it is possible to dial into the system remotely via the telephone network.
The Telecontrol is available in four different version (see separate Telecontrol Specification). To
connect the Telecontrol to the MMM, the "Exclusive" version is required.
The following functions are implemented in the "Exclusive" Telecontrol version:
- Sending messages if there is a fault (SMS, fax, email)
- These messages can be programmed to be allocated to certain people. For example, CHP faults can
be sent to different people than general boiler or system faults.
- Data recording of all CHP values and up to 16 analogue values from the MMM.
The data is depicted on freely configurable graphs.
- Long-term fault message history
- Long-term operating message history
- Establishing user profiles to save individual settings
- Once a user has registered with the Telecontrol and set up a graph according to their individual
criteria, the same graph can be viewed again on another PC without having to reconfigure it.
Please note:
a separate control panel extension is required for this option!
Delivery
As loose accessories for on-site installation