11
Installation information
Types of installation:
■
Floorstanding installation with line entry above
ground level
■
Floorstanding installation with line entry below
ground level
■
Wall mounting
Technical guide
Floorstanding installation:
■
Use supports for floorstanding installation (accesso-
ries).
■
Where such supports cannot be used, install the
external unit freestanding on a solid base of
at least 100 mm height.
■
In difficult climatic circumstances (temperatures
below zero, snow, humidity) install the appliance on
a plinth of approx. 300 mm height.
■
Take into account the weight of the external unit: See
the following table.
Wall mounting:
■
Use the wall mounting bracket set (accessories).
■
The wall must meet the structural requirements.
Positioning:
■
Never install with the discharge side facing the main
wind direction.
■
Provide wall ducts and protective pipes for the refrig-
erant lines and electrical cables without moulded
parts and change of direction.
Weather influences:
■
Observe wind loads when installing the unit on sites
exposed to the wind.
■
Incorporate the external unit into the lightning protec-
tion system.
■
Consider the heat emitted by the unit when planning
your weatherproofing or an enclosure.
Condensate:
■
Ensure the condensate can drain freely, and create a
permanent gravel bed below the external unit as a
soakaway.
■
In regions with prolonged cold seasons (e.g. Swe-
den), provide an electric ribbon heater (accessory)
for the condensate pan.
Insulation against structure-borne noise and vibra-
tions between building and external unit:
■
When line entry is
above
ground level, fit pipe bends
in the refrigerant lines to isolate vibrations: See
"Connecting refrigerant lines".
■
Route electrical cables/leads between the internal
and external units free of stress.
■
Installation only on walls with high weight per area (
>
250 kg/m
2
), in other words not on lightweight walls,
roof structures etc.
■
For floorstanding installation, only use the rubber
mounts supplied.
■
For wall mounting, only use the anti-vibration mounts
from the bracket set.
■
Never use additional anti-vibration mounts, springs,
rubber mounts, etc.
Weight of outdoor units
Type AWT/AWT-AC
Weight in kg
221.A04
43
221.A05
66
221.A07
66
221.A10
113
221.A13
113
221.B10
113
221.B13
113
221.B16
121
Installation sequence
Installing the outdoor unit
5776 028 GB
Installation
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...