50
Type AWB/AWB-E-AC 201.D10 to 201.D16
L1
L2 L3 N
GND Rx/Tx-Rx/Tx+
Modbus
?
B
A
L1
L2 L3 N
?
Fig. 49
A
Outdoor unit wiring chamber: See page 20.
B
Power supply 400 V/50 Hz
Max. cable length
Vitocal 200-S
Type
Cable
Max. cable length
400 V appliances
■
AWB
■
AWB-E-AC
201.D10
5 x 2.5 mm
2
30 m
201.D13
5 x 2.5 mm
2
30 m
201.D16
5 x 2.5 mm
2
30 m
Max. fuse rating
Type AWB/AWB-E-AC
201.D10
201.D13
201.D16
Max. fuse rating
16 A
16 A
16 A
Instantaneous heating water heater power supply
■
Type AWB(-M)-E-AC 201.D:
factory-fitted
■
Type AWB(-M)-E 201.D:
accessories
Installation sequence
Power supply
(cont.)
5790 931 GB