122
Parameter
Setting
Lead heat pump
Lag heat pump
"System definition"
Ó
"Flow temperature for external
demand 730C"
–
"0"
to
"700"
(
≙
0 to
70 °C)
"Communication"
Ó
"Heat pump number in cas-
cade (LON) 5707"
–
"1"
to
"4"
(unique)
"Communication"
Ó
"Enable LON communication
module 7710"
"1"
"1"
"Communication"
Ó
"LON subscriber number
7777"
"1"
to
"99"
(unique)
"1"
to
"99"
(unique)
"Communication"
Ó
"LON system number 7798"
"1"
to
"5"
"1"
to
"5"
(as per lead
heat pump)
"Communication"
Ó
"LON fault manager 7779"
"1"
to
"99"
(unique)
"1"
to
"99"
(unique)
Note
The additional parameters for the heat
pump cascade are set during commis-
sioning by a certified heat pump contrac-
tor.
Instructing the system user
The system installer should hand the
operating instructions to the system user
and instruct the user in operating the
system.
This includes all components installed as
accessories, e.g. remote control units. In
addition, the system installer must make
the user aware of the required mainte-
nance work.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5609 667 GB