The control unit must be matched to the system equip-
ment level.
Set the parameters according to the accessories fitted:
Accessory installation instructions
Adjusting the heating curve
Tap the following buttons:
1.
2.
Use
/
to select
"P.3"
for the heating curve.
3. OK
4.
Use
/
to adjust the slope.
5. OK
6.
Use
/
to adjust the level.
7. OK
to confirm
Instructing the system user
The system installer should hand the operating instruc-
tions to the system user and instruct the user in oper-
ating the system.
This includes all components installed as accessories,
e.g. remote control units. In addition, the system instal-
ler must make the user aware of the required mainte-
nance work.
DHW hygiene
For optimum DHW hygiene, avoid DHW temperatures
that are < 50 °C. For larger systems and systems with
low water exchange, the temperature should not drop
below < 60 °C.
Inform the system user what DHW temperatures
should be set and the risks associated with having a
higher outlet temperature at the draw-off points.
Commissioning, inspection, maintenance