38
Overview of electrical connections
Note
■
Route 230 V~ cables and LV leads separately and
bundle them tightly together at the terminals. This
ensures that, in the event of a fault, e.g. if a wire
becomes detached, the wires cannot drift into the
adjacent voltage area.
■
Strip the cables of a small amount of insulation close
to the terminals.
■
If 2 components are connected to the same terminal,
press both cores together in a
single
wire ferrule.
Wiring chamber, front
Fig. 30
Note
Diagram without terminal covers (see also page 76)
A
Power supply, power circuit (compressor)
3 x 400 V/50 Hz with ON/OFF switch
B
Fuse circuit breaker, NH fuse for power circuit,
compressor 2
C
Fuse circuit breaker, NH fuse for power circuit,
compressor 1
D
Power supply unit 230 VAC/24 VDC
E
UPS module
F
Soft starter, compressor 2
G
Soft starter, compressor 1
Installation procedure, heat pump
Electrical connections
(cont.)
5837251