Viega Grundfix Plus Instructions For Use Manual Download Page 35

In normal operation, the control shows that maintenance is due every

4320 operating hours (=180 operating days).
Display indication:  [Perform maintenance]
The acoustic signal can be switched off by pressing the buttons T1

[Sound off]  and T3. The display goes off after the maintenance has

completed.
There is a pressure switch in the lid of the Grundfix Plus Control which

issues the signal to close the motor-powered flap in case of back pres‐

sure. During cleaning work, the cover must not be cleaned with a high-

pressure cleaner, abrasive cleaning agents, blades or similar cleaning

equipment.
To avoid damage, only clean casing, flap mechanisms and seals with

soft brushes under running water.
The buttons should only be used if the lid is firmly screwed onto the

Grundfix Plus Control.

Choose the menu  [Maintenance]  by pressing button T1 and con‐

firming with button T3.

INFO!

 The display remains unchanged after bringing up the

[Maintenance]  menu. 

Close the motor-powered flap by pressing the button T2.

Set the emergency lock in 

"

ZU

"

 (OFF) position.

Loosen the screws on the lid.

Y

Handling

Grundfix Plus Control backflow trap type 3

35

Summary of Contents for Grundfix Plus

Page 1: ...Instructions for Use Grundfix Plus Control backflow trap type 3 for wastewater pipe containing faeces Model Year built from 4987 41 01 2010 INT...

Page 2: ...3 3 Handling 15 3 1 Assembly information 15 3 1 1 Installation dimensions 15 3 2 Assembly 16 3 2 1 Mount base unit 16 3 2 2 Connecting connection cable and pressure hose 16 3 2 3 Connecting the contro...

Page 3: ...3 6 1 Inspection 33 3 6 2 Maintenance 34 3 6 3 Replacing the rechargeable battery 39 3 7 Disposal 41 Table of contents Grundfix Plus Control backflow trap type 3 3...

Page 4: ...does not extend to possible operating instructions The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use 1 2 Labelli...

Page 5: ...ermany e g DIN DVGW Some passages in the text may refer to technical codes in Europe Germany These should serve as recommendations in the absence of corresponding national regulations The relevant nat...

Page 6: ...nage points beneath the backflow level DIN 1986 100 Requirements in backflow traps type 3 EN 13564 Regulations from section Application areas Scope Notice Regulations applicable in Ger many Grundfix P...

Page 7: ...perature of 95 C with pH values of 4 or 10 The backflow trap is suitable for use in drain pipelines made of HT or sewer pipe DN 100 125 or 150 When using other pipes such as e g clay pipes or cast iro...

Page 8: ...ere is a downward slope to the sewer n the rooms are of lower ranking significance i e neither the inhabi tants health nor major assets would be damaged in case of flooding of the rooms n the system i...

Page 9: ...1 5 4 2 3 Fig 2 Correct place of installation of the backflow trap 1 Street Backflow level 2 Area safe from backflow Product information Grundfix Plus Control backflow trap type 3 9...

Page 10: ...ion and installation conditions on page 6 Backflow protections and their control units should be installed in such a way that they are always accessible The backflow sensor reacts at accumulation heig...

Page 11: ...he backflow trap 1 Measuring funnel 2 Pressure hose 3 connection cable control 4 Motor 5 Pressure switch 6 Emergency lock actuation 7 Lid 8 Casing 9 Emergency lock shutter 10 Motor powered flap Produc...

Page 12: ...ble 10 Outlet for potential free contacts 2 4 2 Technical data Switching power pack 88 264 VAC 50 60 Hz LCD 20 x 2 with lighting RTC real time clock power reserve 30 days rechargeable battery 12 V 1 2...

Page 13: ...operation If the pres sure switch registers the backflow of water the motor powered flap is closed the following display appears Back pressure and a signal sounds every 10 seconds The use of the drai...

Page 14: ...Fig 6 Control elements control unit 1 Menu T1 2 Test T2 3 Reset T3 Product information Grundfix Plus Control backflow trap type 3 14...

Page 15: ...accumulation heights of 100 mm measured from the upper edge of the base pipe line Therefore when planning the installation heights of the existing floor drains out of which water could flow in the cas...

Page 16: ...m line up to the middle of the outlet pipe Close the emergency lock position ZU OFF In this way damage from flooding can be avoided before commis sioning Lay the empty pipe from the base unit to the m...

Page 17: ...n the union nut of the pressure hose slightly using tools Remove the closing cap Plug in the electric plug connection straight NOTICE Make sure that the plug is plugged in straight Connecting the pres...

Page 18: ...e a cable grip device 3 2 3 Connecting the control DANGER Danger due to electrical current An electric shock can lead to burns and serious injury and even death n Only allow electrical work to be carr...

Page 19: ...using the quick connec tion Lead the connection cable via the PG screw fitting into the internal space of the control Attach the cable ends n black n red Insert the rechargeable battery Handling Grun...

Page 20: ...tory fitted rechargeable battery con nection GND 4 red factory fitted rechargeable battery con nection AKKU 5 Green motor connec tion motor 6 Yellow motor connec tion motor 7 signalises back flow R CK...

Page 21: ...se right INFO On delivery the battery fuse is attached to the inside of the casing with adhesive tape NOTICE Depending on the length of the connection cable a jumper may be required to make a connecti...

Page 22: ...ds n The use of a safety transformer in accordance with VDE 0551 or DIN EN 60742 is permitted 3 3 Commissioning 3 3 1 Commissioning the control As soon as the mains voltage is connected the control be...

Page 23: ...switch must be tested using the pressure test Set the emergency lock in ZU OFF position Close the motor powered flap by pressing the button T2 Display Test NRV closed Unscrew the brass plug from the...

Page 24: ...for 10 minutes by replenishing Observe loss If the loss is greater than 0 5 l check and if required replace the seals on the flaps Set the emergency lock to AUF ON position The water drains away Disp...

Page 25: ...owered flap open main supply 230 V Backflow protection is assured Operating condition normal operation Chapter 3 4 2 Operating condition normal operation on page 26 Back pressure NRV closed Motor powe...

Page 26: ...wered emergency operation on page 30 3 4 2 Operating condition normal operation In normal operation control parameters can be entered and information can be called up with the T1 T2 and T3 buttons The...

Page 27: ...log display and self test Note The adjustment from daylight saving time is carried out manually 5x Event memory Back to event memory Call up events one after another Log display 6x Software vers Back...

Page 28: ...time Acoustic signals in case of backflow or error are switched off by pressing T1 button once and confirmed with button T3 During normal operation the motor powered flap can be opened and closed by p...

Page 29: ...buttons have the following functions Function Button Switch off signal Call up Sound off with T1 button and confirm with T3 button Forces motor powered flap to open Keep T3 button pressed for five sec...

Page 30: ...econds can be switched off using T1 button If the rechargeable battery is fully charged 12 V backflow is ensured for n maximum 24 hours when using the 8 m connection cable n maximum 10 hours when usin...

Page 31: ...ery n Control unit n Motor motor powered flap with mechanism n Pressure switch If the control unit registers a defect during the daily self test or due to failure of the mains or battery power the rel...

Page 32: ...e professionals n Check rechargeable battery Recharge able battery fuse n Check cabling Battery error Replace battery Rechargeable battery faulty Operators No safeguarding against back flow in case of...

Page 33: ...ssure NRV closed Display although there is no back flow occur ring Pressure switch defec tive Operators Positive opening with T3 button keep pressed down for 5 seconds Replace cover 1 The components i...

Page 34: ...onal n Only use original parts for repair maintenance and extension n Replace defective components do not repair n When using cameras and cleaning devices cleaning spiral high pressure cleaner protect...

Page 35: ...work the cover must not be cleaned with a high pressure cleaner abrasive cleaning agents blades or similar cleaning equipment To avoid damage only clean casing flap mechanisms and seals with soft brus...

Page 36: ...of the lid Do not grease the spindle Carefully clean the opening for the pressure switch on the lower side of the cover with a small brush Take out and clean the flaps Check seals if necessary replace...

Page 37: ...st be greased with silicon grease Install the flaps Place the lid on and screw it down Open the motor powered flap by pressing button T2 Actuate the emergency lock and check it for smooth function Y H...

Page 38: ...test funnel When the pressure switch is intact the control will report a back flow Display indication Test NRV closed Back pressure NRV closed If necessary a positive opening is possible Press the bu...

Page 39: ...urns to Normal operation after approx 60 sec onds Alternatively normal operation can be activated using buttons T1 and T3 3 6 3 Replacing the rechargeable battery DANGER Risk of electric shock Replace...

Page 40: ...on the connection strip 3 black fac tory fitted rechargeable battery con nection GND 4 red factory fitted rechargeable battery con nection AKKU Insert the replacement battery fuse right comprised in...

Page 41: ...of in accordance with valid national legal requirements Electronic components and batteries must not be put in the domestic waste but must be disposed of appropriately in conformity with the applicabl...

Page 42: ...Viega GmbH Co KG service technik viega de viega com INT 2021 11 VPN210611...

Reviews: