background image

Scope / Notice

Regulations applicable in Ger‐

many

Permitted use with piping mate‐

rials in potable water installations

(PE-HD)

DIN 8074, DIN 8075

Permitted use with piping mate‐

rials in potable water installations

(PE-X)

DIN 16893, DIN 16892

Scope / Notice

Regulations applicable in Ger‐

many

Threshold values for ovalities

DIN 12201-2, Table 1

Scope / Notice

Regulations applicable in Ger‐

many

Leakage test before commis‐

sioning the connection line

DVGW-Arbeitsblatt W 400-2

Leakage test before commis‐

sioning the connection line

DVGW-Arbeitsblatt W 333

Leakage test before commis‐

sioning the connection line

DIN EN 805

2.2

Intended use

Coordinate the use of the model for areas of use and

media other than those described with the Viega Service

Center.

The expression "SC-Contur" appearing in the instructions

for use means "Smart Connect Feature".

2.2.1

Areas of use

The tapping valve is suitable for connecting house service connections

on pressurised water supply pipelines.

Regulations from section: Pipes

Regulations from section: Notes on mounting

Regulations from section: Leakage test

Product information

Geopress tapping valve

6

Summary of Contents for 9690TW

Page 1: ...Instructions for Use Geopress tapping valve for water applications Model Year built from 9690TW 01 2018 AU...

Page 2: ...ping valve 10 2 3 4 Mark on tapping valves 11 2 3 5 Compatible connecting pieces for the tapping valve 11 3 Handling 13 3 1 Transport 13 3 2 Storage 13 3 3 Assembly information 13 3 3 1 Mounting instr...

Page 3: ...and if required maintain this product This restriction does not extend to possible operating instructions In addition the applicable regulations must be observed for potable water house service conne...

Page 4: ...ndards in Europe e g EN and or in Germany e g DIN DVGW Some passages in the text may refer to technical codes in Europe Germany These should serve as recommendations in the absence of corresponding na...

Page 5: ...ice connections DIN EN 805 Planning execution operation and maintenance of potable water house service connections DVGW Arbeitsblatt W 400 1 Planning execution operation and maintenance of potable wat...

Page 6: ...0 2 Leakage test before commis sioning the connection line DVGW Arbeitsblatt W 333 Leakage test before commis sioning the connection line DIN EN 805 2 2 Intended use Coordinate the use of the model fo...

Page 7: ...600 kPa 16 bar 2 2 3 Replacing a damaged tapping valve CAUTION A hole must be drilled in accordance with Chapter 3 4 3 Tapping the supply line on page 20 to make a tight con nection The tapping valve...

Page 8: ...el is available in the following dimensions d 63 90 110 125 140 160 180 200 2 3 2 Pipes The tapping valve is suitable for the connection of house service con nections on supply lines under pressure in...

Page 9: ...d use with piping materials d mm PE HD 1 SDR 11 17 6 PE X 1 SDR 11 13 6 63 90 110 125 140 160 180 200 1 see Regulations from section Pipes on page 6 Potable water Product information Geopress tapping...

Page 10: ...ps the pressing force on the pipe at a con stant level The integrated cutter is connected to the actuating spindle The cutter is used for tapping and subsequently remains in the fitting The cutter hol...

Page 11: ...pipeline parts must be documented and regularly updated The traceability code on the tapping valve allows every con nector to be traced back and simplifies the documentation in as com pleted drawings...

Page 12: ...is integrated into the Viega product network At the outlet of the tapping valve the house service connection is connected by means of a connecting piece or connection elbow Product information Geopres...

Page 13: ...he opposite side of the outlet sleeve Pipes must be visually inspected for the following damage before instal lation n Ovalities threshold values must not be exceeded see Regula tions from section Not...

Page 14: ...eat of the tapping valve For the Z dimensions refer to the respective product page in the online catalogue 3 3 3 Required tools The following tools are required for mounting the tapping valve n Batter...

Page 15: ...Fig 4 Pressgun 5 Recommended Viega press machines n Pressgun 5 with rechargeable battery n Pressgun 4B with rechargeable battery Handling Geopress tapping valve 15...

Page 16: ...g point is 5 x DN however at least 0 5 m from pipe con nections or other pipe fittings n Information about the supply line to be tapped are available n General manufacturer s information n Experience...

Page 17: ...ng valve at the prepared point on the supply pipe Push the bottom part of the pipe clamp into the first notch until it snaps into place Alignment Turn the marking on the tapping valve centrally to the...

Page 18: ...nnection is pressed Place the hinged adapter jaw Z2 accurately in the seat of the tap ping valve Carry out the pressing process until the machine switches off Connection is pressed Hit the fixing bolt...

Page 19: ...ing piece as far as it will go into the outlet sleeve Place the clamping ring around the connecting piece and mount the fixing bolt Mount the house service connection in accordance with the instruc ti...

Page 20: ...r 3 4 6 Leakage test on page 22 Screw the spindle in as far as possible using a ratchet or a spanner Unscrew the spindle to open the operation shut off 3 4 4 Commission the house service connection Ch...

Page 21: ...any position Delivery sizes Setting ranges m n 0 70 1 00 n 1 00 1 50 n 1 25 1 80 n 1 50 2 00 If the tapping valve is operated with another support it is possible to prevent dirt entering the sleeve pi...

Page 22: ...e maximum operating pressure once the mains pipe has been tapped Carry out the test on a house service connection that is finished but not yet covered The result of the leakage test must be documented...

Page 23: ...Viega Pty Limited support viega com au viega com au AU 2019 09 VPN190451...