VIDEX ART.280N1 USER INSTRUCTIONS 

  

25/06/2002                      PAGE 6 of  8                    VERSION 1.6 

  

280InstN2. 

 

 

LOCK RELEASE

12V AC

~ ~

0.1uF capacitor

 

 
 

 

+

-

1N4002

+

-

12V DC

LOCK RELEASE

DIODE

 

 
 

Cable size and type : 

When running cables for any intercom system, these 

cables must be installed separately from the mains cables. All multipair 
cables should be to CW1308 specification.  (0.5mm twisted pair telephone 
cable). Max resistance = 10 Ohm.  
Lock release wires should be doubled up. Max resistance = 3 Ohm 
The cables sizes above can be used for distances up to 50m. On distances 
above 50m the cable sizes should be increased to keep the overall resistance 
of the cable below the RESISTANCE’S indicated above. 
 
The total length of standard telephone wiring between the primary and  each 
extension socket must not exceed 50M. The total length from the primary 
socket to the furthest secondary socket must not exceed 100M.  
 

Dimensions

 The ART280 is enclosed in a standard 9 module DIN box. (157.5mm 

Long x 105mm wide x 65mm high). 

The DIN module can either be mounted directly to the wall or  onto a DIN rail.

 

Summary of Contents for 280N1

Page 1: ...n 6 Telephone line or mains interference can cause problems for the Artr280N1 to identify DTMF tones Connections to the telephone line Each telephone line coming into your home or office must be fitte...

Page 2: ...per P must be fitted The telephone line cord is now redundant and should not be used NOTE 2 After each programming function the handset must be replaced The system is programmed from the telephone key...

Page 3: ...access code This access code will be used only when the call is diverted Pick up the telephone and press RECALL RECALL 4 Four digit access code A confirmation tone will be heard from the earpiece for...

Page 4: ...et you will be connected with the caller To receive a call from the door panel A quick double ring will be heard from the phone Pick up the handset you will be connected to the door panel If you then...

Page 5: ...or output Enter the Access code 6 To end the call before timeout Enter the Access code 7 Note This will also switch the divert off To switch divert back off Pickup the handset and press RECALL RECALL...

Page 6: ...oubled up Max resistance 3 Ohm The cables sizes above can be used for distances up to 50m On distances above 50m the cable sizes should be increased to keep the overall resistance of the cable below t...

Page 7: ...al assurance of successful operation on every PSTN network termination point In the event of problems you should contact your equipment supplier in the first instant Your Art 280 telephone interface i...

Page 8: ...ion 3 The lock is not wired correctly to the Art280 The Art280 has a dry contact relay output across C NO These two terminals short together when the door open is activated The Art280 does not activat...

Page 9: ......

Reviews: