26
8. TECHNICAL SPECIFICATION
Quattro
24/5000/120-100/100
48/5000/70-100/100
PowerControl / PowerAssist
Yes
Integrated Transfer switch
Yes
AC inputs (2x)
Input voltage range: 187-265 VAC Input frequency: 45 – 55 Hz Power factor: 1
Maximum feed through current (A)
AC-in-1: 100A AC-in-2: 100A
Minimum PowerAssist current (A)
AC-in-1: 11A AC-in-2: 11A
INVERTER
Input voltage range (V DC)
19 – 33
38 – 66
Output
(1)
Output voltage: 230 VAC ± 2% Frequency
:
50 Hz ± 0,1%
Cont. output power at 25 °C (VA)
(3)
5000
5000
Cont. output power at 25 °C (W)
4500
4500
Cont. output power at 40 °C (W)
4000
4000
Peak power (W)
10000
10000
Maximum efficiency (%)
94
95
Zero-load power (W)
25
25
CHARGER
Charge voltage 'absorption' (V DC)
28,8
57,6
Charge voltage 'float' (V DC)
27,6
55,2
Storage mode (V DC)
26,4
52,8
Charge current house battery (A)
(4)
120
70
Charge current starter battery (A)
4
Battery temperature sensor
yes
GENERAL
Auxiliary AC output
Max load: 50A Switches off when in inverter mode
Multi purpose relay
(5)
Yes, 3x
Protection
(2)
a - g
VE.Bus communication port
For parallel and three phase operation, remote monitoring and system integration
General purpose comm. port
Yes, 2x
Common Characteristics
Operating temp.: -20 to +50°C (fan assisted cooling) Humidity (non condensing) : max 95%
ENCLOSURE
Common Characteristics
Material & Colour: aluminium (blue RAL 5012) Protection: IP 21
Battery-connection
Four M8 bolts (2 plus and 2 minus connections)
230 V AC-connection
M6 bolts
Weight (kg)
31
Dimensions (hxwxd in mm)
444 x 328 x 240
STANDARDS
Safety
EN 60335-1, EN 60335-2-29
Emission / Immunity
EN55014-1, EN 55014-2, EN 61000-3-3
1) Can be adjusted to 60 Hz and to 240V
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25 °C ambient
5) Programmable relays which can be set for general alarm, DC undervoltage or genset start signal function
AC rating: 230V/4A
DC rating: 4A up to 35VDC, 1A up to 60VDC
Summary of Contents for Quattro 24
Page 2: ......
Page 4: ......
Page 58: ......
Page 114: ......
Page 161: ...19 EN NL FR DE ES SE Appendix Er ro r float Err or Ob temperatur ...
Page 171: ...29 EN NL FR DE ES SE Appendix Er ro r float Err or Ob temperatur ...
Page 190: ......
Page 191: ...1 EN NL FR DE ES SE Appendix APPENDIX A Overview connections ...
Page 196: ...6 APPENDIX C Parallel connection ...
Page 197: ...7 EN NL FR DE ES SE Appendix APPENDIX D Three phase connection ...
Page 200: ...10 APPENDIX G Dimensions ...
Page 201: ......
Page 202: ......
Page 203: ......