22
Step 1: Setting ds2 and ds1 for 3-phase operation
As the table above shows, the current limits for each phase should be set separately (ds8 thru ds5). Thus, for AC-in1 as well as AC-in-
2, different current limits per phase can be selected.
If a panel is connected, the AC-in-2 current limit will equal the value set on the panel for all phases.
The maximum charging current is the same for all devices, and should be set on the leader (ds4 and ds3).
Example:
-
AC-in-1 current limitation on the leader and the followers: 16A (setting for generator power 16 x 230 x 3 = 11kVA).
-
AC-in-2 current limitation with 16A panel.
-
If the charging current on the leader is set to 100% (120A for a Quattro 24/5000/120) and the system consists of three
devices, then the effective system charging current is equal to 3 x 120 = 360A.
The settings according to this example (15kVA 3-phase system) are as follows:
To store the settings after the required values have been set: press the 'Up' button of the
leader
for 2 seconds (
upper
button to the
right of the DIP switches, see appendix A, position K).
The overload and low-battery LEDs will flash to indicate acceptance of the
settings
.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
Leader (L1)
Follower (L2)
Follower (L3)
DS-8 AC-in-1 (16A)
off
DS-7 AC-in-1 (16A)
on
DS-6 AC-in-1 (16A)
on
DS-5 AC-in-2 Not relevant (16A panel)
DS-4 Charging current (3 x 120 = 360A)
on
DS-3 Charging current (3 x 120 = 360A)
on
DS-2 Leader
on
DS-1 Leader
off
DS-8 AC-in-1 (16A)
off
DS-7 AC-in-1 (16A)
on
DS-6 AC-in-1 (16A)
on
DS-5 Not relevant
DS-4 Not relevant
DS-3 Not relevant
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 AC-in-1 (16A)
off
DS-7 AC-in-1 (16A)
on
DS-6 AC-in-1 (16A)
on
DS-5 Not relevant
DS-4 Not relevant
DS-3 Not relevant
DS-2 Slave 2
off
DS-1 Slave 2
on
Leader (L1)
Follower (L2)
Follower (L3)
DS-8 AC-in-1 Set as desired
DS-7 AC-in-1 Set as desired
DS-6 AC-in-1 Set as desired
DS-5 AC-in-2 Set as desired
DS-4 Charging current Set as desired
DS-3 Charging current Set as desired
DS-2 Leader
on
DS-1 Leader
off
DS-8 Set as desired
DS-7 Set as desired
DS-6 Set as desired
DS-5 Set as desired
DS-4 Not relevant
DS-3 Not relevant
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 Set as desired
DS-7 Set as desired
DS-6 Set as desired
DS-5 Set as desired
DS-4 Not relevant
DS-3 Not relevant
DS-2 Slave 2
off
DS-1 Slave 2
on