6. MAINTENANCE 

 
The Compact does not require specific maintenance. It will suffice to check all 
connections once a year. Avoid moisture and oil/soot/vapours, and keep the device clean. 
 
 
 

7. TROUBLE SHOOTING TABLE 

 
Proceed as follows for quick detection of common faults. 
 
Consult your Victron Energy dealer if the fault cannot be resolved. 
 

 

Problem 

Cause 

Solution 

The inverter fails 
to operate when 
switched on. 

The battery voltage is too high 
or too low. 

Ensure that the battery voltage 
is within the correct value.  

The inverter fails 
to operate 

Processor in no function-mode. 

Switch Front switch off, wait 4 
seconds 
Switch front switch on.  

The alarm LED 
flashes. 

Pre-alarm alt. 1. The DC input 
voltage is low. 

Charge the battery or check the 
battery connections. 

The alarm LED 
flashes 

Pre-alarm alt. 2. The ambient 
temperature is too high. 

Place the inverter in a cool and 
well-ventilated room, or reduce 
the load.  

The alarm LED 
flashes. 

Pre-alarm alt. 3. The load on the 
inverter is higher than the 
nominal load. 

Reduce the load.  

The alarm LED 
flashes. 

Pre-alarm alt. 4. Voltage ripple 
on the DC input exceeds 
1.25Vrms. 

Check the battery cables and 
terminals. 
Check the battery capacity; 
increase if necessary. 

The alarm LED 
flashes 
intermittantly. 

Pre-alarm alt. 5. Low battery 
voltage and excessive load. 

Charge the batteries, reduce 
the load or install batteries with 
a higher capacity. Use shorter 
and/or thicker battery cables. 

The alarm LED is 
on  

The inverter did cut out following 
a pre-alarm. 

Check the table for the 
appropriate course of action.  

Summary of Contents for Phoenix Inverter 24/3000

Page 1: ...os usar el inversor cargador MultiPlus en vez de este El conmutador está incluido es este producto y la función de cargador del MultiPlus puede deshabilitarse Los ordenadores y demás equipos electrónicos continuarán funcionando sin interrupción ya que el MultiPlus dispone de un tiempo de conmutación muy corto menos de 20 milisegundos Interfaz para el ordenador Todos los modelos disponen de un Puer...

Page 2: ...Capacidad nominal CA 230V 4A Capacidad nominal CC 4 A hasta 35VDC 1 A hasta 60VDC 4 Protección a Cortocircuito de salida b Sobrecarga c Tensión de la batería demasiado alta d Tensión de la batería demasiado baja e Temperatura demasiado alta f 230 V CA en la salida del inversor g Ondulación de la tensión de entrada demasiado alta Phoenix Inverter Control This panel can also be used on a MultiPlus i...

Page 3: ... Battery H UTP Cable Remote control J AC OUT G K Battery Link 1x 2x12V 1 100mm 100mm 100mm B A A D C D 3 1 2 10 3 5 8 4 6 7 9 Not included Included M F E T sense V sense G I MAIN MAIN TRICKLE H DIGITAL MULTI CONTROL I H L L N GND L N GND AC OUT 1 AC OUT 2 L N L N GND AC IN 1 AC IN 2 F TR charge G V sense E T sense N K J N O O 24V 48V F MAIN E J I AC OUT L N GND H G ...

Page 4: ...Manual EN Handleiding NL Manuale FR Anleitung DE Manual ES Appendix Phoenix Inverter Compact 12 1200 230V 24 1200 230V 12 1600 230V 24 1600 230V ...

Page 5: ......

Page 6: ...Y PRODUCTS AND MAKES SUCH VICTRON ENERGY PRODUCTS AVAILABLE SOLELY ON AN AS IS BASIS IN NO EVENT SHALL VICTRON ENERGY B V BE LIABLE TO ANYONE FOR SPECIAL COLLATERAL INCIDENTAL OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING OUT OF PURCHASE OR USE OF THESE VICTRON ENERGY PRODUCTS THE SOLE AND EXCLUSIVE LIABILITY TO VICTRON ENERGY B V REGARDLESS OF THE FORM OF ACTION SHALL NOT EXCEED THE PURC...

Page 7: ......

Page 8: ...in conjunction with the battery Always comply with the battery manufacturer s safety instructions WARNING Do not lift heavy loads without assistance Installation Read the installation instructions in the installation manual before installing the equipment This is a Safety Class I product supplied with a protective grounding terminal The chassis must be grounded A grounding point is located on the ...

Page 9: ...product No liability can be accepted for any transport damage if the equipment is shipped in non original packaging Store the product in a dry environment the storage temperature must be between 20 C and 60 C Consult the battery manufacturer s manual in respect of transport storage charging recharging and disposal of the battery ...

Page 10: ...er the load to another AC source the automatic transfer switch If an automatic transfer switch is required we recommend to using the MultiPlus or Quattro instead The switch is included in these products and the charger function of the MultiPlus Quattro can be disabled Computers and other electronic equipment will continue to operate without disruption because the MultiPlus Quattro features a very ...

Page 11: ... switched on and supplies power to the load Battery operation inverter on eco mode off alarm eco The inverter is switched on and supplies power to the load Pre alarm overload or battery voltage low or inverter temperature high inverter on eco mode off alarm eco The inverter is switched off Alarm overload or battery voltage low or inverter temperature hig or DC ripple voltage on battery terminal wa...

Page 12: ...nting see appendix A The appliance can be mounted horizontally as well as vertically vertical mounting is preferable The vertical position offers optimum cooling Try and keep the distance between the product and the battery to a minimum in order to minimize cable voltage losses For safety purposes this product should be installed in a heat resistant environment if it is used with equipment where a...

Page 13: ... resistance is the important factor when working with low capacity batteries Please consult your supplier or the relevant sections of our book electricity on board downloadable from our website Procedure Proceed as follows to connect the battery cables Use an insulated box spanner in order to avoid shorting the battery Avoid shorting the battery cables Connect the battery cables the red and the bl...

Page 14: ...ight N neutral earth and L1 phase Use a three wire cable with a flexible core and a cross section of 1 5 or 2 5 mm 4 4 Optional Connections A number of optional connections are possible 4 4 1 Remote on off switch remote Control panel The product can be remotely controlled in two ways With an external switch connection terminal H see appendix A Operates only if the switch on the Inverter is set to ...

Page 15: ...oint must at least equal the sum of the required cross sections of the connections between the distribution point and the inverters Place the inverters close to each other but allow at least 10 cm for ventilation purposes under above and beside the units UTP cables must be connected directly from one unit to the other and to the remote panel Connection splitter boxes are not permitted Only one rem...

Page 16: ...r frequency Output frequency Adjustability 50Hz 60Hz Inverter voltage Adjustability 210 245V Stand alone parallel operation 2 3 phase setting Using several devices it is possible to Increase total inverter power several devices in parallel Create a split phase system Create a 3 phase system The standard product settings are for standalone operation For parallel three phase or split phase operation...

Page 17: ...t down 40 Watt linear load Turn on 100 Watt linear load AES Automatic Economy Switch Instead of the search mode the AES mode can also be chosen with help of VEConfigure only If this setting is turned on the power consumption in no load operation and with low loads is decreased by approx 20 by slightly narrowing the sinusoidal voltage Not adjustable with DIP switches Applicable in stand alone confi...

Page 18: ...connection to the computer a RJ45 UTP cable and the MK2 2b RS485 to RS232 interface is required If the computer has no RS232 connection but does have USB a RS232 to USB interface cable is needed Both are available from Victron Energy 5 3 2 VE Bus System Configurator and dongle For configuring advanced applications and or systems with four or more inverters VE Bus System Configurator software must ...

Page 19: ...all DIP switches of a new product are set to off except for DS 2 DS 1 Panel option off DS 2 Panel option on DS 3 Not used DS 4 Not used DS 5 Frequency DS 6 Search mode off DS 7 Not used DS 8 Store setting DS 1 off DS 2 on DS 3 DS 4 DS 5 off DS 6 off DS 7 DS 8 DS 1 on DS 2 off DS 3 DS 4 DS 5 on DS 6 on DS 7 DS 8 Example 1 factory setting 1 No panel connected 2 No panel connected 5 Frequency 50Hz 6 ...

Page 20: ...shes Pre alarm alt 1 The DC input voltage is low Charge the battery or check the battery connections The alarm LED flashes Pre alarm alt 2 The ambient temperature is too high Place the inverter in a cool and well ventilated room or reduce the load The alarm LED flashes Pre alarm alt 3 The load on the inverter is higher than the nominal load Reduce the load The alarm LED flashes Pre alarm alt 4 Vol...

Reviews: