manual
17
victron energy
3. TECHNICAL DATA
3.1 Phoenix xx/220
TECHNICAL DATA
Ph 12/220
Ph 24/220
Ph 48/220
Cont. output at 25°C
4)
220VA
220VA
220VA
Cont. output power at 25°C
1)
175W 175W 175W
Cont. output power at 40°C
1)
150W 150W 150W
Peak power
350W
400W
400W
Output voltage
230Vac
±
2% or 115Vac
±
2%
Output frequency
50Hz
±
0.05% or 60Hz
±
0.05%
Output waveform
True sinewave
Total harmonic distortion
Maximum 5%
3)
Admissible cos
ϕ
of load
0.6 – 1
Input voltage (±3% tol.):
Nominal 12Vdc
24Vdc
48Vdc
Range 10.5
2)
– 16Vdc 21
2)
– 31Vdc 41
2)
– 60Vdc
Maximum efficiency
90%
91%
93%
No load power consumption at
nominal input voltage
[economy]
< 2.8W
[0.6W]
< 3W
[0.8W]
< 4W
[1.2W]
Operating temperature range
(ambient)
-20
°
C to +50
°
C
Economy threshold
Pout = 12W
Pout = 15W
Pout = 15W
Protections against
Short circuit, overload, high temperature and
low battery voltage
Indications (by pre-
programmed flashing
sequences of the power LED)
Power on, short circuit/overload, high
temperature, high/low battery voltage and
economy mode
DC input connection
Two wires, length 1.5 meters,
∅
4mm²
AC output connection
IEC-320 AC outlet
Enclosure body size
(l x h x w)
154 x 98 x 130 (without mounting brackets)
Protection class
IP20
Total weight
2.3 kg
2.3 kg
2.4 kg
The inverter complies with the
following standards :
EN50081-1 Generic Emissions Standard
EN50082-1 Generic Immunity Standard
EN60335-2 Safety Standard