18
Step 2: Exemplary settings
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to ‘off’ and do
not reflect the actual settings in the microprocessor.).
DS-8 Ch. voltage
off
DS-7 Ch. voltage
on
DS-6 Absorpt. time
on
DS-5 Adaptive ch.
on
DS-4 Dyn. Curr. limit
off
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
DS-8
off
DS-7
off
DS-6
on
DS-5
on
DS-4
off
DS-3
off
DS-2
on
DS-1
on
DS-8
on
DS-7
off
DS-6
on
DS-5
on
DS-4
on
DS-3
off
DS-2
off
DS-1
on
DS-8
on
DS-7
on
DS-6
off
DS-5
off
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 120V
1 Frequency: 50Hz
Step 2
Example 2:
8, 7 OPzV 14,1V
6 Abs. time: 8 h
5 Adaptive ch.: on
4 Dyn. Curr. limit: off
3 UPS function: off
2 Voltage: 120V
1 Frequency: 50Hz
Step 2
Example 3:
8, 7 AGM 14,7V
6 Abs. time: 8 h
5 Adaptive ch: on
4 Dyn. Curr. limit: on
3 UPS function: off
2 Voltage: 120V
1 Frequency: 50Hz
Step 2
Example 4:
8, 7 Tub.-plate 15V
6 Abs. time: 4 h
5 Fixed abs. time
4 Dyn. Curr. limit: off
3 UPS function: on
2 Voltage: 120V
1 Frequency: 60Hz
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (
lower
button to the right of the DIP
switches).
The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
The DIP switches can be left in the selected positions, so that the ’other settings’ can always be recovered.
Summary of Contents for MultiPlus 3000
Page 2: ......
Page 26: ......
Page 27: ...EN Appendix APPENDIX A Overview connections ...
Page 29: ...EN Appendix APPENDIX B Block diagram See table in Chapter 4 2 Recommended DC fuse ...
Page 34: ...APPENDIX G Dimensions ...
Page 35: ...EN Appendix ...
Page 36: ......
Page 37: ......