7. Technical Specifications
Multi RS Solar
48/6000
INVERTER
DC Input voltage range
38 – 64V
Output
Output voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
Continuous output power at 25°C
Increases linearly from 4800W at 46 VDC to 5300W at 52 VDC
Continuous output power at 40°C
4500W
Continuous output power at 65°C
3000W
Peak power
9kW for 3 seconds
Short-circuit output current
74 A
Max. AC output overcurrent
protection
30 A
Maximum efficiency
96.5% at 1 kW load
94% at 5 kW load
Zero load power
20W
Low battery shutdown
37.2 V (adjustable)
Low battery restart
43.6 V (adjustable)
SOLAR
Maximum DC voltage
450 V
Start-up voltage
120 V
MPPT voltage range (2)
80 – 450 V
Maximum operational PV input
current
18 A
Max. PV short circuit current
reverse polarity protection (3)
20A
Max. PV short circuit current (Isc
PV)
30A
Earth leakage trip level
30 mA
Isolation fail level
(detection before start-up)
100 kΩ
CHARGER
Programmable charger voltage
range (2)
Minimum: 36 V
Maximum 62 V
Charge voltage 'absorption'
default: 57.6 V
Charge voltage 'float'
default: 55.2 V
Maximum charge current (4)
100 A
Maximum DC charging power
4000 W
Battery temperature sensor
Included
Battery voltage sense
Yes
GENERAL
Parallel and 3-phase operation
No
Auxiliary output
No
Programmable relay (5)
Yes
Multi RS Solar
Page 37
Technical Specifications