3
LED INDICATIONS
3.1
Lynx Ion + Shunt LED indications
Firmware version 1.22 and higher.
Status LED state
Description
Off
System is in standby mode. Press START button to start
up the system
Blinking fast
Initialization.
On
Running
Blinking
Balancing active
Flashing/beeping 1 time
Battery initialization error
Flashing/beeping 2 times
No batteries connected
Flashing/beeping 3 times
Unknown battery connected / battery connected to a
running system.
Flashing/beeping 4 times
Different types of batteries connected
Flashing/beeping 5 times
Number of connected batteries incorrect
Flashing/beeping 6 times
Shunt fault
Flashing/beeping 7 times
Battery measure error occurred
Flashing/beeping 8 times
Internal calculation error
Flashing/beeping 9 times
Number of batteries in series incorrect
Flashing/beeping 10 times
Number of batteries incorrect (only used when using
static number of battery configuration)
Flashing/beeping 11 times
Not used
Flashing/beeping 12 times
Not used
Flashing/beeping 13 times
Over voltage
Flashing/beeping 14 times
Under voltage
Flashing/beeping 15 times
Over temperature
Flashing/beeping 16 times
Under temperature
Flashing/beeping 17 times
ADC data error
Blinking/beeping fast
Battery BMS error (slave)
Flashing 3 times (no beeping)
Battery BMS warning (slave)
Flashing/beeping 18 times
Pre-Charge error
Flashing/beeping 19 times
Safety contactor error
Flashing 2 times (no beeping)
Over current error on External status or external safety
contactor output (appendix A connector B)
Summary of Contents for Lynx Ion + Shunt 350
Page 1: ......
Page 2: ......
Page 4: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 14: ......
Page 15: ......
Page 17: ...4 Configure the Lynx Ion BMS Support assistant as follows ...
Page 23: ......
Page 24: ...Front view I G H J ...
Page 25: ......
Page 28: ......
Page 29: ...Distributor Serial number Version 1 Date 10 June 2014 ...