5.5.2. DIP switch 3 to 7
These DIP switches can be used to set:
- Battery charge voltage and Absorption time
- Inverter frequency
- Search mode
- AC input current limit 12A or 6A
ds3-ds4: Setting charge voltages
ds3-ds4
Absorption
voltage
Float
voltage
Storage
Voltage
Absorption
Time
(hours)
Suitable for
ds3=off
ds4=off
(default)
14.4
28.8
57.6
13.8
27.6
55.2
13.2
26.4
52.8
8
Gel Victron Deep Discharge
Gel Exide A200
AGM Victron Deep Discharge
ds3=on
ds4=off
14.1
28.2
56.4
13.8
27.6
55.2
13.2
26.4
52.8
8
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV)
Gel MK battery
ds3=off
ds4=on
14.7
29.4
58.8
13.8
27.6
55.2
13.2
26.4
52.8
5
AGM Victron Deep Discharge
Tubular plate or OPzS
batteries in semi-float mode
AGM spiral cell
ds3=on
ds4=on
15.0
30.0
60.0
13.8
27.6
55.2
13.2
26.4
52.8
6
Tubular plate or OPzS
batteries in cyclic mode
Batteries with high antimony content can typically be charged with a lower absorption voltage
than batteries with low antimony content. (Please refer to our book ‘Electricity on Board’
downloadable from our website www.victronenergy.com for details and suggestions about
charging batteries). Contact your battery supplier for the correct charge voltages and change
(with VE-configure) the voltage settings if required.
The default charge current setting is 75% of the maximum charge current. This current will be
too high for most applications.
For most battery types the optimal charge current is 0.1-0.2x the battery capacity.
ds5: Inverter frequency
off = 50Hz
on = 60Hz
ds6: Search Mode
off = off
on = on
ds7: AC input current limit
off = 12Amp
on = 4Amp
Store the settings by moving DIP switch 8 to ‘on’ and back to ‘off’.
Summary of Contents for EasySolar 12 1600
Page 2: ......
Page 32: ...30 ...
Page 62: ......
Page 92: ......
Page 122: ......
Page 153: ...31 EN NL FR DE ES Appendix ...
Page 154: ......
Page 155: ...EN NL FR DE ES Appendix www victronenergy com Appendix A overview connections ...
Page 156: ...Appendix B installation information ...
Page 157: ...EN NL FR DE ES Appendix www victronenergy com Appendix C Inverter PCB connections ...
Page 158: ...Appendix D DIP switches ...
Page 159: ......