12
minutes) ensures that long term load fluctuations are included in
the time-to-go calculations.
DF:
Discharge floor.
When the state-of-charge percentage has fallen
below this value, the alarm relay will be activated. The time-to-go
calculation is also linked to this value. It is recommended to keep
this value at around 50.0%.
ClS:
Clear SOC relay.
When the state-of-charge percentage has risen
above this value, the alarm relay will be de-activated. This value
needs to be greater than or equal to DF.
RME:
Relay minimum enable time.
Specifies the minimum amount of
time that the alarm relay should be enabled once an alarm
condition has occurred.
RDD:
Relay disable delay.
Specifies how long you have to wait before
disabling the relay; after the alarm condition has cleared.
Al:
Alarm low voltage (buzzer).
When the battery voltage falls below
this value for more than 10 seconds a bell icon appears on the
display, the backlight flashes, and the buzzer will sound. The
buzzer and backlight-flashing can be turned off by pressing any
key; the bell-icon will remain on the display.
Alc:
Clear low voltage alarm.
When the battery voltage rises above
this value, the alarm is turned off. This value needs to be greater
than or equal to Al.
Ah:
Alarm high voltage (buzzer).
When the battery voltage rises
above this value for more than 10 seconds a bell icon appears on
the display, the backlight flashes, and the buzzer will sound. The
buzzer and backlight-flashing can be turned off by pressing any
key; the bell-icon will remain on the display.
Ahc:
Clear high voltage alarm.
When the battery voltage falls below
this value, the alarm is turned off. This value needs to be less than
or equal to Ah.
AS:
Alarm low SOC (buzzer).
When the state-of-charge falls below
this value for more than 10 seconds a bell icon appears on the
display, the backlight flashes, and the buzzer will sound. The
buzzer and backlight-flashing can be turned off by pressing any
key; the bell-icon will remain on the display.
ASc:
Clear low SOC alarm.
When the state-of-charge rises above this
value, the alarm is turned off. This value needs to be greater than
or equal to AS.
Rl:
Relay low voltage.
When the battery voltage falls below this value
for more than 10 seconds the alarm relay will be activated.