Trouble Diagnosis for the User
Malfunction

Possible Cause

Likely Solution

No cooling - unit is silent

Unit not plugged in.
Fuse or circuit breaker tripped. 
Power cord plug loose in outlet.

Connect to proper voltage circuit Replace 
fuse or reset breaker.
Check outlet for loose connection, replace 
as needed

Unit cools but seems to be on all the time

Dirty condenser

Clean condenser

Space temperature too high

Dirty condenser
Evaporator iced over Unit in high 
temperature environment

Clean condenser Defrost evaporator
Reduce temperature of room

Space temperature too low

Temperature control   

Adjust or replace control

Trouble Diagnosis for the Technician
No cooling - compressor does not hum

Temp control stuck in open position

Replace temp control.

No cooling - compressor hums but does not 
start

Low voltage to unit.
Compressor starting  system failure

Check voltage, correct as needed. Check 
start relay and start capacitor. See next 
step.

No cooling - compressor starts but shuts 
off

Compressor start relay failure Compressor 
start capacitor failure

Replace relay. Replace capacitor.

No cooling - compressor cycles on and off

Overheating weak overload

Clean condenser, check fan motor and 
blade. Check refrigerant charge. Replace 
overload.

Unit cools, but is slow to pull cabinet 
temperature down

Evaporator fan not turning

Check fan(s), on multiple fan units one fan 
may be turning slowly and will need to be 
replaced.

Unit cools but turns on and off frequently

No product in cabinet. Temperature control 
defective Refrigeration issue

Fill cabinet Replace control
Have system checked

Makes excessive noise    

Tubing rattle Loose parts
Bent or broken fan blade Noisy fan motor

Check tubing for routing Check for loose 
components Replace fan blade
Replace fan motor

Summary of Contents for ACRS-1D-S1-G-HC

Page 1: ...UCTIONS for all Hydrocarbon ACRS Air Curtain Refrigerator Models 3779 CHAMPION BLVD WINSTON SALEM NC 27105 Phone 888 845 9800 Fax 800 253 5168 Web victoryrefrigeration com 809 197A 02 05 2021 SEE BACK...

Page 2: ...roperly register equipment may limit or void the warranty Victory reserves the right to change specifications and product design without notice Such revisions do not entitle the buyer to corresponding...

Page 3: ...ying in or on the cabinet Persons unable to use this product must be prevented access Follow all instructions There are many safety labels and directions on the unit Heed them Watch your fingers There...

Page 4: ...u models with rubber bumpers and heavy duty non marking casters Since the condensing unit is located at the base of the cabinet there is a low center of gravity making it more stable when transporting...

Page 5: ...for units that have been altered in any way Alterations or part substitutions will void the warranty Limitations The machine is designed for use indoors in a controlled environment It must be kept dry...

Page 6: ...Solid ACRS 1D S1 G HC 29 x 36 1 4 x 78 7 8 Glass ACRS 1D S1 PT G SD HC 31 1 4 x 36 1 2 x 78 7 8 Glass PRODUCT INFORMATION Refrigerator will maintain product temperature between 36 and 38 degrees F at...

Page 7: ...The floor on which the Refrigerator is located must be even and level free from vibrations and strong enough to support the combined weights of the unit and maximum product load Ventilation Grille ar...

Page 8: ...any product with a glass door Skid Removal 1 Unbolt unit from skid by unhooking brackets on sides of unit anchored to vertical pieces of skid 2 Remove protective vinyl coating from all interior and ex...

Page 9: ...an tray slide into the square cut out and press down to lock in place Align the front tab with the square cut out and press down locking it as shown Line up both front and back tabs with the cut outs...

Page 10: ...5 20P plug If the power cord becomes damaged it must be replaced with the identical cord Follow All National and Local Codes This unit must be grounded Do not use extension cords and do not disable or...

Page 11: ...e of the cabinet keeping it out of the way when loading or unloading product Those models have tracks on the side and hinge plates on the door that engage those tracks Open the door normally until it...

Page 12: ...rature faster When on the refrigeration system is always operating at maximum The temperature was set at the factory at 36 F but you can adjust it to your own selected temperature See page 17 The Refr...

Page 13: ...and allow to temper in the ACRS for approximately 2 hours 2 All pans should be placed on slides to ensure the best performance of the unit 3 After product is loaded allow cabinet to pull down to temp...

Page 14: ...R FAN The Evaporator Fan runs continuously whenever the unit is plugged in The Evaporator Fan is connected to line voltage The Evaporator Fan runs continuously whenever the unit is plugged in The Evap...

Page 15: ...nently On Defrost active Blinking Activated manually or from Digital input OFF Otherwise 3 Fans Permanently On Fans active OFF Otherwise 4 Reduced SET Economy Permanently On Energy saving active Blink...

Page 16: ...Display connection 15 16 17 LIGHT STANDBY UP DOWN ESC SET Enter Press and Hold Press and Hold Press and Release Press and Release Press and Release Press and Release Long press 5 sec Toggles light on...

Page 17: ...tive Key pad will beep when unlocked and normal key pad operations performed Setting the Operating Set Point To change the operating set point press and release the set button to enter the machine men...

Page 18: ...ed Press the set button to display the value and use the up or down button to change the value Once the value has been selected use the escape button to confirm the new value and return the pervious m...

Page 19: ...User Manual for ACRS Air Curtain Refrigerators Victory Rev 02 21 Victory 19...

Page 20: ...atic SP1 Att Afd HA1 PAO dAO OAO tA1 AH2 HIGH temperature 2 alarm ON Active Automatic SP2 Att Afd HA2 PAO dAO OAO tA2 AL2 LOW temperature 2 alarm ON Active Automatic SP2 Att Afd HA2 PAO dAO OAO tA2 EA...

Page 21: ...orine 2 Rinse with clean water 3 Dry with a soft cloth 4 Polish with a soft cloth wiping with the grain 5 Wipe weekly with stainless steel cleaner Weekly Interior Cleaning 1 Remove all food food relat...

Page 22: ...ss grille at the bottom front of the cabinet 3 Examine condenser surface if dusty brush and vacuum the dust and lint from the surface of the coil Brush up and down to avoid damaging the fins Use care...

Page 23: ...small amount of cleaner Heat tint or discoloration Penny Brite or Copper Brite Past NuSteel DuBois Temp or Tarnite Revere Stainless Steel Cleaner Allen Polish Steel Bright Tenacious Deposits Rusty Di...

Page 24: ...temp control No cooling compressor hums but does not start Low voltage to unit Compressor starting system failure Check voltage correct as needed Check start relay and start capacitor See next step N...

Page 25: ...e venting MUST be in an area free from flame or spark It must be near an opened window or door A sign noting service of a system containing propane must be attached to the unit during refrigeration se...

Page 26: ...OVERLOAD CONTROLLER TERMINAL CONNECTION POINT 1 E T I H W K C A L B CNTRL 3 1 VAPORIZER HEATER CONTROL THERMOSTAT VAPORIZER EVAP FAN EVAP SENSOR AIR SENSOR NOT USED NOT USED NOT USED 6 DIGITAL INPUT...

Page 27: ...tlined in the Owner s Manual adjustment of door mechanisms or freight damage are not covered by this warranty For the purpose of this warranty the original purchaser shall be deemed to mean the indivi...

Page 28: ...GIVEN IN LIEU OF ALL OTHER WARRANTIES EXPRESS IMPLIED OR STATUTORY INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH ARE HEREBY DISCLAIMED AND ALL OTHER OB...

Page 29: ..._________________ Date Of Installation _________________ Cabinet Serial Number _____________________________________________ Location Of Product Business Name _________________________________________...

Reviews: