background image

10

PROBLEM

POSSIBLE CAUSE

REMEDY

Controller Display does 
not illuminate

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Power cord unplugged

Plug in power cord to designated receptacle. 
Cabinet cannot share same outlet with other 
equipment.

Control or main power switch turned off

Turn on control or main power switch (refer 
to page 3 "

V-TEMP

 

Keypad  Buttons &  

Functions" section)

Cabinet not running

Improper voltage supplied to cabinet 
(voltage does not match Data-Plate)

Correct supply voltage (remove extension cords 
or other equipment on circuit, etc).

Controller set too high

Set controller to lower temperature

Cabinet in defrost cycle

Allow defrost cycle to fi nish

Condensing Unit on 
Refrigerator or Freezer 
runs for prolonged 
period or continuously

Excessive amount of warm product loaded 
in cabinet

Allow adequate time for product to cool down

No product in cabinet

Load cabinet with product

Prolonged door opening or door ajar

Make sure door is closed when not in use. Avoid 
prolonged door openings.

Door gasket not sealing properly

Check door gasket condition. Adjust door or 
replace gasket.

Dirty condenser coil

Clean the condenser coil

Improper air fl ow around condensing unit

Insure adequate air space, relocate away from 
heat generating equipment, direct sunlight, or 
direct path of air conditioning or heating ducts

Evaporator coil blocked with ice

Turn unit off and allow coil to defrost. Make sure 
controller temperature is not set too low and that 
door gasket is sealing properly.

Refrigerator or Freezer 
cabinet temperature too 
high

Controller set too high

Set controller to lower temperature

Poor air circulation in cabinet

Re-arrange product to allow proper air circulation

Excessive amount of warm product loaded 
in cabinet

Allow adequate time for product to cool down

Prolonged door opening or door ajar

Make sure door is closed when not in use. Avoid 
prolonged door openings.

Dirty condenser coil

Clean the condenser coil

Insuffi cient clearance around cabinet or 
excessively high ambient temperature

Insure adequate air space, relocate away from 
heat generating equipment (ovens, fryers, heating 
ducts, etc.), and out of direct sunlight

Evaporator coil blocked with ice

Turn unit off and allow coil to defrost. Make sure 
controller is not set too cold and that door gasket 
is sealing properly.

Cabinet is noisy

Part(s) loose

Locate and tighten loose part(s)

Tubing vibrating

Insure tubing is free from contact with other 
tubing or components

Refrigerator is freezing 
product

Controller set too low

Set controller to higher temperature

Cabinet overloaded with product

Remove or re-arrange product

Refrigerator or Freezer 
compressor will not 
start - hums and trips 
on overload protector

Dirty condenser coil

Clean the condenser coil

Excessive heat generated from nearby 
equipment

Relocate cabinet or adjust heat generating 
equipment

Voltage to cabinet too high or too low

Check and correct supply voltage

Door won't close tight

Cabinet is not level

Level cabinet by adjusting legs or shimming 
casters

Hinge(s) may need slight adjusting.

Apply shim(s) to hinge until door seals properly.

Controller Alarm & 
Error Codes

----

Refer to page 5 of manual. If problem(s) persist, 
contact the factory for further assistance.

TROUBLESHOOTING GUIDE FOR COMMON PROBLEMS

TROUBLESHOOTING GUIDE FOR COMMON PROBLEMS

Caution:

Caution: Disconnect Power Supply Prior To Attempting Any Service! 

 Disconnect Power Supply Prior To Attempting Any Service! 

Summary of Contents for 50707412

Page 1: ...ng Manual 110 Wo o d crest Roa d C he rry H ill N J 0 8003 Phone 856 428 4200 Fax 856 673 0038 Website www victoryrefrigeration com E Mail parts victoryrefrigeration com order entry victoryrefrigerati...

Page 2: ...RTANT INFORMATION PLEASE READ Please read these instructions carefully before installing or using If recommended procedures are not followed warranty claims may be denied Your Warranty Registration in...

Page 3: ...d bill from the servicing agency must accompany the claim together with full details of the service problems diagnosis and work performed Victory will determine at its sole discretion whether further...

Page 4: ...ning through a filter dryer first to remove any dirt or foreign particles D Defrost The term is used to identify the function of a refrigerator or freezer to remove frost or ice from the internal evap...

Page 5: ...rs 6 7 PERIODIC CLEANING Cabinet Cleaning 8 Condenser Maintenance 8 Lubrication 9 Installing Replacement Door Gasket 9 TROUBLESHOOTING GUIDE FOR COMMON PROBLEMS Common Problems Remedies 10 COMMON REPL...

Page 6: ...ion as possible before removing skid 4 Remove the shipping skid by tipping the cabinet forward Remove the shipping bolts with 3 4 box wrench while the cabinet is held in one direction Repeat this proc...

Page 7: ...a dedicated circuit with separate grounding wire is required Controller When first supplying power to the cabinet there will be approximately a one minute delay before the compressor and fan motors s...

Page 8: ...ation KEYPAD BUTTONS Note Use V TEMP Keypad illustration above to follow these instructions Button 1 ON STANDBY Press this button for a few seconds to switch the cabinet on and off Button 2 MANUAL DEF...

Page 9: ...This requires the user to press a button to clear the alarm The HACCP LED provides information regarding the memory status of the HACCP alarms If it is on not all of the information regarding the HAC...

Page 10: ...when the defrost terminates on time rather than temperature a Verify that the evaporator probe is intact and in the evaporator coil b Press any button to restore normal display The unit will continue...

Page 11: ...erval is required set this to 4 Calendar The Hd parameters must be set to the time defrosts are required d20 Max Time for Safety Defrost in Normal Operation N A 120 0 500 This parameter is used to set...

Page 12: ...rost 20 20 min 0 240 This parameter is used to initiate a defrost if the door has been open continuously for this amount of time Outputs Configuration Parameters u9 Buzzer enabling Enabled Enabled Dis...

Page 13: ...temperature Condenser Maintenance To keep your cabinet running efficiently it is recommended that you clean the condenser coil once every three months or immediately after the COH LED displays and ala...

Page 14: ...ed Removing Beginning at one corner pry the gasket loose from the retaining strip Peel remainder of the gasket from the door and discard Replacing Before replacing be sure the gasket and door are at r...

Page 15: ...ture Poor air circulation in cabinet Re arrange product to allow proper air circulation Excessive amount of warm product loaded in cabinet Allow adequate time for product to cool down Prolonged door o...

Page 16: ...inet Narrow Extra Wide 50617203 Evaporator Coil 86E10 1 Section Freezer 1 per cabinet Narrow Extra Wide 50616902 Evaporator Coil 86E21 2 3 Section Freezer 1 per cabinet Narrow Extra Wide 50639401 Evap...

Page 17: ...r Half Lower Left Hinged with S S Liner 1 per refrigerator freezer half section 10848813 Door Extra Wide Half Upper Right Hinged with S S Liner 1 per EW 1 2 section half door refrig frzr 10848814 Door...

Page 18: ...13 WIRING DIAGRAMS WIRING DIAGRAMS 1 2 3 Section Refrigerator Wiring Diagram for 115 Volt 15 Amp 20 Amp 1 2 3 Section Refrigerator Wiring Diagram for 115 Volt 208 230 Volt Condensing Unit...

Page 19: ...14 1 2 3 Section Freezer Wiring Diagram for 115 Volt 15 Amp 20 Amp 1 2 3 Section Freezer Wiring Diagram for 115 Volt 208 230 Volt Condensing Unit...

Page 20: ...t Roa d C he rry H ill N J 0 8003 Phone 856 428 4200 Fax 856 673 0038 Website www victoryrefrigeration com E Mail parts victoryrefrigeration com order entry victoryrefrigeration com service victoryref...

Reviews: