UG:119
Page 23
Environmental Characteristics
Storage Temperature
–40 to 85°C
Altitude
De-rate 2.6% total output power for each 1,000ft to a maximum operating
altitude of 15,000ft. Non-operating storage maximum altitude is 40,000ft.
Operating Temperature
[g]
–20 to 40°C full power; –20 to 60°C half power
Humidity
0 – 95% non-condensing
Safety Agency Approvals
cURus – UL 60950-1, CSA 60950-1
cTUVus – EN 60950-1, UL 60950-1, CSA 60950-1
CE Mark – Low Voltage Directive, 73/23/EEC amended by 93/68/EEC
Product Weights
(fully configured)
PFC MegaPAC-EL™
PFC MegaPAC-HPEL™
12.8lbs [5,8 kgs]
13.1lbs [6 kgs]
Warranty
2 years limited warranty.
See
for complete warranty statement.
See Vicor module specifications. A preload may be necessary for modules trimmed down below 90% of
normal output voltage.
[g]
The maximum operating temperature is 40°C. If using a VI-200 with output voltage less than 12V and more than
150W, the operating temperature decreases to 35°C. This also applies when using a FinQPAC™ with output voltage
less than 24V and more than 500W.
Output Studs
New, more robust output studs (with a 3:1 safety margin at 45lbs.in) were installed in ConverterPACs™,
the slide-in assemblies used in the MegaPAC™ Family. These new outputs studs are 1/8" longer to
allow for multiple lugs. They are fully compatible with the original flanged nut ConverterPACs for use in
parallel arrays.
Other advantages include:
n
n
Inner nut (that might become loose) replaced by a brass insert
n
n
Stronger connection to the PCB
n
n
Improved conductivity (less voltage drop and heating)
n
n
Both the stud and panel are less likely to break due to over torqueing
Shown below are the original and redesigned studs.
Refer to Page 14 for dimensional data.
Original
Redesigned